0 battery sense wire kits, 1 36v single and dual strings, Fig. 8-1, 36v system, single string – Alpha Technologies DSM3 for XM3 - Technical Manual User Manual

Page 79: Fig. 8-2, 36v system, dual string

Advertising
background image

79

745-814-B11-001, Rev. C (03/2014)

8.1

36V Single and Dual Strings

Fig. 8-1, 36V System, Single String

Sense Wire Kits:

Alpha P/N: 874-842-21 (6')

Alpha P/N: 874-842-27 (9')

Fig. 8-2, 36V System, Dual String

Sense Wire Kits:

Alpha P/N: 874-842-20 (6')

Alpha P/N: 874-842-28 (9')

8.0 Battery Sense Wire Kits

Communications Module Battery Sense Wire Kits are required for individual battery voltage

monitoring when the XM3 SAG option is not installed. For XM3 power supplies with the SAG option,

it is recommended to use the specific SAG wire kits or the SAG adapter kits to accommodate any

existing Communications Module Battery Sense Wire Kits. Otherwise, a SAG "No Harness" alarm will

be generated if the Battery Sense Wire Kits are connected to the Communications Module battery

connections (A/B or C/D) instead of the SAG connector.

ug

Back of Pl

1

2

3

4

5

6

7

8

Vbatt 3A

[C] 36V

Pin 4

3A

POS

NEG

2A

POS

NEG

1A

POS

NEG

A/B [C/D] NEG

Pin 1

Vbatt 2A

[C] 24V

Pin 3

Vbatt 1A

[C] 12V

Pin 2

To Power Supply

Black

Red

(-)

(-)

(-)

(+)

(+)

(+)

POS

POS

POS

3B

NEG

2B

NEG

1B

NEG

Back of Plug

3A

POS

NEG

2A

POS

NEG

1A

POS

NEG

A/B [C/D] NEG

Pin 1

Vbatt 3A

[C] 36V

Pin 4

Vbatt 2A

[C] 24V

Pin 3

Vbatt 1A

[C] 12V

Pin 2

Vbatt 3B [D] 36V

Pin 7

Vbatt 2B [D] 24V

Pin 6

Vbatt 1B [D] 12V

Pin 5

To Power Supply

Red

Black

(-)

(-)

(-)

(+)

(+)

(+)

1

2

3

4

5

6

7

8

Advertising