745-814-B11-001, Rev. C (03/2014)

DSM3x

DSM3

DPM

Power Supply Monitored Parameters

Major Alarm:

Aggregate alarm consisting of: Test fail, battery fail, line isolation alarm, output overload, inverter,

over-temperature, N+1 active, fuse fail

Minor Alarm:

Aggregate alarm consisting of: Temperature probe error, AC line loss, N+1 error

Input Voltage:

Reported from power supply V(in) measurement

Output Voltage:

Reported from power supply V(out) measurement

Output Current:

0 to 25A standard on port 1

Port 2 requires power suppy DOC option

Output Power:

Calculated; reported in AC Watts

Input Current:

Reported in Amps

Input Power:

Reported in Amps

UPS Status:

AC Line, Standby, Test in progress, Test alarm

Charger Current:

Reported in Amps

Battery Discharge Current:

Reported in Amps

Enclosure Door:

Open or Closed

Battery Voltage:

Individual battery voltage, up

to four strings of 3 batteries

(maximum 12 batteries),

±100mV per battery.

Individual battery voltage,

up to two strings of 3

batteries (maximum 6

batteries), ±100mV per

battery.

Individual battery voltage, up to

four strings of 3 batteries

(maximum 12 batteries),

±100mV per battery.

(Requires SAG option)

Battery Temperature:

Reported from power supply battery Remote Temperature Sensor (RTS)

Remote Test Control:

Start/Stop power supply test cycle

Generator Monitored Parameters (DSM3x Only)

Status:

Generator Off, Running, Alarm

Generator Alarm:

Aggregate alarm consisting of: Low oil pressure, engine over-temp, engine over-speed, crank limit,

over voltage, low fuel, water intrusion, pad shear, gas hazard, test fail

Gas Hazard:

OK, Alarm

Water Intrusion:

OK, Alarm

Pad Shear:

OK, Alarm

Enclosure Door:

OK, Alarm

Ignition Battery Voltage:

Reported in DC volts, ±100mV

Enclosure Temperature:

Reported in Celcius, ±2°C

Low Fuel:

OK, Alarm

Remote Test Control:

Start / Stop generator test cycle

Cable Modem

Compliance:

DOCSIS 1.1 and 2.0

EuroDOCSIS 2.0

Transmit Frequency Range:

5 to 42 MHz

5 to 65 Mhz

Receive Center Frequency Range:

91 to 857 MHz

112 to 858 Mhz

Output Power Range:

TDMA:

+8 to +54 dBmV (32QAM, 64QAM)

+8 to +55 dBmV (8QAM, 16QAM)

+8 to +58 dBmV (QPSK)

S-CDMA:

+8 to +53 dBmV (All modulations of S-CDMA)

TDMA:

+68 to +114 dBuV (32QAM, 64QAM)

+68 to +115 dBuV (8QAM, 16QAM)

+68 to +118 dBuV (QPSK)

S-CDMA:

+68 to +113 dBuV (All modulations of S-CDMA)

Input Signal Range:

-15 to 15 dBmV

64QAM: 43 to 73 dBuV

256QAM: 47 to 77 dBuV

Channel Bandwidth:

6 MHz

8 Mhz

Additional Equipment

874-842-21 XP-BSC-3-6:

Wire Kit, Battery Sense, 1x36V, 6'

874-842-20 XP-BSC-6-6:

Wire Kit, Battery Sense, 2x36V, 6'

Surge Arrestor

(Alpha p/n 162-028-10):

Female/Female connector configuration, “F” type connector with integral ground block. Required for

all installations

11.0 Specifications