Table 6-8, Power Alarms: Classifications, Causes and Corrections

Active Alarm

Alarm type

Alarm Category

Probable Cause of Alarm

Corrective action

Standby Disabled

Self Test FAIL

Major

PWR

Output voltage failed or batteries less than 1.85V/C during

Self Test.

1. Check Batteries

2. Check Inverter

NO

LINE ISOLATION

Major

PWR

Line isolation has failed and Inverter operations are

suspended.

1. Replace Power Supply as soon as

possible

YES

OUTPUT FAILURE

Major

PWR

The AC output has failed due to a bad Inverter or

transformer.

1. Apply load >1.5A

2. Output Overloaded

3. Check Inverter

NO

OUTPUT OVERLOAD

Major

PWR

The output is overloaded or shorted.

1. Output Short Circuit

2. Check Output Current

NO

OUTPUT 1 TRIPPED

Major

PWR

Output 1 AlphaDOC hardware protection mode is engaged

and overloaded.

1. Over Current

2. Check Settings

NO

OUTPUT 2 TRIPPED

Major

PWR

Output 2 AlphaDOC hardware protection mode is engaged

and overloaded.

1. Over Current

2. Check Settings

NO

CHARGER FAILURE

Major

PWR

Charger has failed to shut down; possible battery over

temperature condition exists.

1. Re-seat Inverter

2. Perform Self Test

NO

INVERTER TEMP

Major

PWR

Inverter heat sink has exceeded set temperature. (Stand-

by operations suspended until temperature drops to a

safe level.)

1. Check Inverter

2. Check PDB

3. Check Enclosure Ventilation

NO

CONFIG ERROR

Major

PWR

The Power Supply is improperly configured and

operation is suspended until error is corrected.

1. Wrong Input Voltage or Frequency

NO

INVERTER ALARM/

INVERTER FAILED

Major

PWR

No output detected with good batteries for 30 seconds

OR inverter is disconnected from PDB.

1. Re-seat Inverter

2. Replace Inverter

YES

INPUT FAILURE

Minor

PWR

Utility AC input has failed.

1. Utility Failure

2. Check Input Breaker

3. Input Connections

NO

INPUT OVER CURR /

INPUT CURRENT LIMIT

Minor

PWR

AC Input current exceeds threshold setting.

1. Reduce Output Load

2. Check Input Current Limit Setting

NO

SURGE MOV FAIL

Minor

PWR

The MOV board surge protection has failed and needs

to be replaced.

1. Replace MOV Board

NO

ALPHADOC OPTION

Minor

PWR

I2C has failed between XM3 and DOC.

1. Check Ribbon Cable

2.Replace DOC

NO

INVERTER ENABLE

Minor

PWR

System controller has disabled the Inverter.

1. Check Inverter

YES

CHARGER ENABLE

Minor

PWR

System controller has disabled the charger.

1. Check Charger

NO

APP OPTION

Minor

PWR

I2C has failed between XM3 and APP.

1. Check Ribbon Cable

2. Replace APP

NO

INV EEPROM ERROR

Minor

PWR

There has been an error reading the EEProm on the

inverter board.

1. Replace Inverter

NO

HW COMPATIBILITY

Minor

PWR

There is a hardware incompatiblity between the main

micro board and the inverter board.

1.Check Micro Board

2.Check Inverter Brd

NO

PDB EEPROM ERROR

Minor

PWR

There has been an error reading the EEProm on the

PDB.

1.Replace Power Supply

NO