0 alpha mib parameters, Parameter oid description access type value, 1 definitions and settings – Alpha Technologies DSM3 for XM3 - Technical Manual User Manual
Page 90
90
745-814-B11-001, Rev. C (03/2014)
Parameter
OID
Description
Access
Type
Value
COUNTERS
atiBBSysViewCounters
1.3.6.1.4.1.926.1.4.1.1.4
Object Identifier
atiBBSysViewSelfTestInterval
1.3.6.1.4.1.926.1.4.1.1.4.1
Number of days between automated Self Tests
Read-Write
Integer
0..65535
atiBBSysViewSelfTestCountdown
1.3.6.1.4.1.926.1.4.1.1.4.2
Number of days until the next automated Self Test
Read-Write
Integer
0..65535
atiBBSysViewSelfTestDuration
1.3.6.1.4.1.926.1.4.1.1.4.3
Number of minutes for which an automated Self
Test will run
Read-Write
Integer
0..65535
atiBBSysViewInverterRuntime
1.3.6.1.4.1.926.1.4.1.1.4.4
Number of minutes the inverter has run due to an
AC fail event
Read Only
Integer
0..65535
atiBBSysViewStandbyEvents
1.3.6.1.4.1.926.1.4.1.1.4.5
Number of times the inverter has gone into standby
due to an AC fail event
Read Only
Integer
0..65535
atiBBSysViewRuntimeRemaining
1.3.6.1.4.1.926.1.4.1.1.4.6
Seconds of estimated runtime remaining when in
standby
Read Only
Integer
0..65535
atiBBSysViewTimeInStandby
1.3.6.1.4.1.926.1.4.1.1.4.7
Seconds. If currently in standby, time in standby. If
not in standby this value will be zero
Read Only
Integer
0..-1
atiBBSysViewTimeSinceLastStandby
1.3.6.1.4.1.926.1.4.1.1.4.8
Seconds. The accumulated time since the end of
last standby event and the start of the next standby
event. The counter will reset to zero after the next
standby event has ended.
Read Only
Integer
0..-1
atiBBSysViewTimeInLastStandby
1.3.6.1.4.1.926.1.4.1.1.4.9
Seconds. The length (time) of last standby event.
If currently in a standby event this value will be the
length of the previous standby event. This value will
be updated at the conclusion of each standby event.
This item is saved in non-vol memory.
Read Only
Integer
0..-1
PLATFORMS
atiProductPlatforms
1.3.6.1.4.1.926.1.4
Object Identifier
atiBroadbandUPS
1.3.6.1.4.1.926.1.4.1
Object Identifier
atiBBSysView
1.3.6.1.4.1.926.1.4.1.1
Object Identifier
atiBBSysViewSelects
1.3.6.1.4.1.926.1.4.1.1.1
Object Identifier
atiBBSysViewSelfTestControl
1.3.6.1.4.1.926.1.4.1.1.1.1.0
Starts/Stops a system Self Test
Read/Write
Integer
1=Stop
2=Start
atiBBSysViewSelfTestInhibit
1.3.6.1.4.1.926.1.4.1.1.1.2.0
System Self Test is prevented. On reset, the DSM
gets this value from the master XM3 (in a system
with more than one power supply).
Read/Write
Integer
1=Normal (default)
2=Inhibited
atiBBSysViewSystemControlMgr
1.3.6.1.4.1.926.1.4.1.1.1.3.0
If the System Control Manager is running, the Small
System Controller/Administrator (SSC or SSA)
is running and there is coordination between the
power supplies for charging, testing, etc. The value
of this item is stored in non-volatile memory.
Read/Write
Integer
1=Running
2=Disabled
SYSTEM ALARMS
atiBBSysViewAlarms
1.3.6.1.4.1.926.1.4.1.1.2
Object Identifier
atiBBSysViewMajorAlarm
1.3.6.1.4.1.926.1.4.1.1.2.1.0
Indicates if any of the items monitored are in a major
alarm state
Read Only
Integer
1=OK
2=Alarm
atiBBSysViewMinorAlarm
1.3.6.1.4.1.926.1.4.1.1.2.2.0
Indicates if any of the items monitored are in a minor
alarm state
Read Only
Integer
1=OK
2=Alarm
atiBBSysViewSelfTestResult
1.3.6.1.4.1.926.1.4.1.1.2.3.0
If any of the items being monitored indicate that Self
Test failed, this item indicates a failure.
Read Only
Integer
1=OK
2=Fail
atiBBSysViewTempProbeStatus
1.3.6.1.4.1.926.1.4.1.1.2.4.0
If any of the devices being monitored indicate a
temp probe failure or absence, this item will alarm.
Read Only
Integer
1=OK
2=Missing
atiBBSysViewInputStatus
1.3.6.1.4.1.926.1.4.1.1.2.5.0
If ALL the items being monitored indicate no AC, this
item will alarm.
Read Only
Integer
1=OK
2=No AC Present
10.1
Definitions and Settings
10.0 Alpha MIB Parameters