0 alpha mib parameters, Parameter oid description access type value, 1 definitions and settings – Alpha Technologies DSM3 for XM3 - Technical Manual User Manual

Page 90

Advertising
background image

90

745-814-B11-001, Rev. C (03/2014)

Parameter

OID

Description

Access

Type

Value

COUNTERS

atiBBSysViewCounters

1.3.6.1.4.1.926.1.4.1.1.4

Object Identifier

atiBBSysViewSelfTestInterval

1.3.6.1.4.1.926.1.4.1.1.4.1

Number of days between automated Self Tests

Read-Write

Integer

0..65535

atiBBSysViewSelfTestCountdown

1.3.6.1.4.1.926.1.4.1.1.4.2

Number of days until the next automated Self Test

Read-Write

Integer

0..65535

atiBBSysViewSelfTestDuration

1.3.6.1.4.1.926.1.4.1.1.4.3

Number of minutes for which an automated Self

Test will run

Read-Write

Integer

0..65535

atiBBSysViewInverterRuntime

1.3.6.1.4.1.926.1.4.1.1.4.4

Number of minutes the inverter has run due to an

AC fail event

Read Only

Integer

0..65535

atiBBSysViewStandbyEvents

1.3.6.1.4.1.926.1.4.1.1.4.5

Number of times the inverter has gone into standby

due to an AC fail event

Read Only

Integer

0..65535

atiBBSysViewRuntimeRemaining

1.3.6.1.4.1.926.1.4.1.1.4.6

Seconds of estimated runtime remaining when in

standby

Read Only

Integer

0..65535

atiBBSysViewTimeInStandby

1.3.6.1.4.1.926.1.4.1.1.4.7

Seconds. If currently in standby, time in standby. If

not in standby this value will be zero

Read Only

Integer

0..-1

atiBBSysViewTimeSinceLastStandby

1.3.6.1.4.1.926.1.4.1.1.4.8

Seconds. The accumulated time since the end of

last standby event and the start of the next standby

event. The counter will reset to zero after the next

standby event has ended.

Read Only

Integer

0..-1

atiBBSysViewTimeInLastStandby

1.3.6.1.4.1.926.1.4.1.1.4.9

Seconds. The length (time) of last standby event.

If currently in a standby event this value will be the

length of the previous standby event. This value will

be updated at the conclusion of each standby event.

This item is saved in non-vol memory.

Read Only

Integer

0..-1

PLATFORMS
atiProductPlatforms

1.3.6.1.4.1.926.1.4

Object Identifier

atiBroadbandUPS

1.3.6.1.4.1.926.1.4.1

Object Identifier

atiBBSysView

1.3.6.1.4.1.926.1.4.1.1

Object Identifier

atiBBSysViewSelects

1.3.6.1.4.1.926.1.4.1.1.1

Object Identifier

atiBBSysViewSelfTestControl

1.3.6.1.4.1.926.1.4.1.1.1.1.0

Starts/Stops a system Self Test

Read/Write

Integer

1=Stop
2=Start

atiBBSysViewSelfTestInhibit

1.3.6.1.4.1.926.1.4.1.1.1.2.0

System Self Test is prevented. On reset, the DSM

gets this value from the master XM3 (in a system

with more than one power supply).

Read/Write

Integer

1=Normal (default)
2=Inhibited

atiBBSysViewSystemControlMgr

1.3.6.1.4.1.926.1.4.1.1.1.3.0

If the System Control Manager is running, the Small

System Controller/Administrator (SSC or SSA)

is running and there is coordination between the

power supplies for charging, testing, etc. The value

of this item is stored in non-volatile memory.

Read/Write

Integer

1=Running
2=Disabled

SYSTEM ALARMS
atiBBSysViewAlarms

1.3.6.1.4.1.926.1.4.1.1.2

Object Identifier

atiBBSysViewMajorAlarm

1.3.6.1.4.1.926.1.4.1.1.2.1.0

Indicates if any of the items monitored are in a major

alarm state

Read Only

Integer

1=OK
2=Alarm

atiBBSysViewMinorAlarm

1.3.6.1.4.1.926.1.4.1.1.2.2.0

Indicates if any of the items monitored are in a minor

alarm state

Read Only

Integer

1=OK
2=Alarm

atiBBSysViewSelfTestResult

1.3.6.1.4.1.926.1.4.1.1.2.3.0

If any of the items being monitored indicate that Self

Test failed, this item indicates a failure.

Read Only

Integer

1=OK
2=Fail

atiBBSysViewTempProbeStatus

1.3.6.1.4.1.926.1.4.1.1.2.4.0

If any of the devices being monitored indicate a

temp probe failure or absence, this item will alarm.

Read Only

Integer

1=OK
2=Missing

atiBBSysViewInputStatus

1.3.6.1.4.1.926.1.4.1.1.2.5.0

If ALL the items being monitored indicate no AC, this

item will alarm.

Read Only

Integer

1=OK
2=No AC Present

10.1

Definitions and Settings

10.0 Alpha MIB Parameters