10.1 Definitions and Settings

The following tables display commonly-configured Alpha MIB parameters and provide specific information

with regard to functionality, options, OIDs, types and variables.

Parameter

OID

Description

Access

Type

Value

atiMgntSnmp

1.3.6.1.4.1.926.1.3.1.0

Object

Identifiers

SNMP TRAP ADDRESSES
atiMgmtSnmpTrapTable

1.3.6.1.4.1.926.1.3.1.1

Object

Identifiers

atiMgmtSnmpTrapAddress.1

1.3.6.1.4.1.926.1.3.1.1.1.2.1

SNMP Trap Address (1)

Read/Write

IP Address

0.0.0.0 (default)

atiMgmtSnmpTrapAddress.2

1.3.6.1.4.1.926.1.3.1.1.1.2.2

SNMP Trap Address (2)

Read/Write

IP Address

0.0.0.0

atiMgmtSnmpTrapAddress.3

1.3.6.1.4.1.926.1.3.1.1.1.2.3

SNMP Trap Address (3)

Read/Write

IP Address

0.0.0.0

atiMgmtSnmpTrapAddress.4

1.3.6.1.4.1.926.1.3.1.1.1.2.4

SNMP Trap Address (4)

Read/Write

IP Address

0.0.0.0

atiMgmtSnmpTrapServerAddressType.1

1.3.6.1.4.1.926.1.3.1.1.1.3.1

Address mode of

atiMgmtSnmpTrapServerAddress (1)

Read/Write

Integer

1: IPv4(1)

2: IPv6(2)

atiMgmtSnmpTrapServerAddressType.2

1.3.6.1.4.1.926.1.3.1.1.1.3.2

Address mode of

atiMgmtSnmpTrapServerAddress (2)

Read/Write

Integer

1: IPv4(1)

2: IPv6(2)

atiMgmtSnmpTrapServerAddressType.3

1.3.6.1.4.1.926.1.3.1.1.1.3.3

Address mode of

atiMgmtSnmpTrapServerAddress (3)

Read/Write

Integer

1: IPv4(1)

2: IPv6(2)

atiMgmtSnmpTrapServerAddressType.4

1.3.6.1.4.1.926.1.3.1.1.1.3.4

Address mode of

atiMgmtSnmpTrapServerAddress (4)

Read/Write

Integer

1: IPv4(1)

2: IPv6(2)

atiMgmtSnmpTrapServerAddress.1

1.3.6.1.4.1.926.1.3.1.1.1.4.1

Address of trap server (1)

Read/Write

IP Address

0.0.0.0 (default)

atiMgmtSnmpTrapServerAddress.2

1.3.6.1.4.1.926.1.3.1.1.1.4.2

Address of trap server (2)

Read/Write

IP Address

0.0.0.0 (default)

atiMgmtSnmpTrapServerAddress.3

1.3.6.1.4.1.926.1.3.1.1.1.4.3

Address of trap server (3)

Read/Write

IP Address

0.0.0.0 (default)

atiMgmtSnmpTrapServerAddress.4

1.3.6.1.4.1.926.1.3.1.1.1.4.4

Address of trap server (4)

Read/Write

IP Address

0.0.0.0 (default)

SECURE SNMP ACCESS ADDRESS
atiMgmtSnmpAccessTable

1.3.6.1.4.1.926.1.3.1.2

Object

Identifiers

atiMgmtSnmpAccessAddress.1

1.3.6.1.4.1.926.1.3.1.2.1.2.1

Secure IP Address (1)

Read/Write

IP Address

0.0.0.0 (default)

atiMgmtSnmpAccessAddress.2

1.3.6.1.4.1.926.1.3.1.2.1.2.2

Secure IP Address (2)

Read/Write

IP Address

0.0.0.0

atiMgmtSnmpAccessAddress.3

1.3.6.1.4.1.926.1.3.1.2.1.2.3

Secure IP Address (3)

Read/Write

IP Address

0.0.0.0

atiMgmtSnmpAccessAddress.4

1.3.6.1.4.1.926.1.3.1.2.1.2.4

Secure IP Address (4)

Read/Write

IP Address

0.0.0.0

SNMP ACCESS ENABLE
atiMgntSnmpAccess

1.3.6.1.4.1.926.1.3.1.3.0

Object

Identifiers

atiMgmtSnmpSnmpv1Access

1.3.6.1.4.1.926.1.3.1.3.1.0

SNMPv1 Access to Power Supply

Data

Read/Write

Integer

1 = Disable
2 = Enable (Default)

atiMgmtSnmpSnmpv2Access

1.3.6.1.4.1.926.1.3.1.3.2.0

SNMPv2c Access to Power Supply

Data

Read/Write

Integer

1 = Disable
2 = Enable (Default)

CPE & SECURITY KEY (Dual IP)
atiMgmtSnmpAlphaSetAccess

1.3.6.1.4.1.926.1.3.1.3.3.0

"Set to Data Access Key
CIBSET (default)"

Read/Write

Octet String

Set to match the value

of the Data Access Key

atiMgmtSnmpAlphaSetKey)

atiMgmtSnmpAlphaSetKey

1.3.6.1.4.1.926.1.3.1.3.4.0

Data Access Key (Dual IP)

Read/Write

Octet String

CIBSET (default)

atiMgmtSnmpCPESetEnabled

1.3.6.1.4.1.926.1.3.1.3.5.0

Corresponds to whether

or not the action taken on

atiMgmtSnmpAlphaSetKey was

successful. Once enabled, writing

1(false) to this variable will disable

CPE sets.

Read/Write

Integer

1=Disabled (False)
2=Enabled (True)

atiMgmtSnmpSnmpCPEAccess

1.3.6.1.4.1.926.1.3.1.3.6.0

Enables the CPE interface - Dual

IP mode

Read/Write

Integer