Brooks, Digital mfc's and mfm's – Brooks Instrument SLAMf Series User Manual

Page 43

Advertising
background image

3-9

Section 3 Operation

Installation and Operation Manual
X-TMF-SLAMf-MFC-eng
Part Number: 541B032AAG
April, 2013

Brooks

®

Digital MFC's and MFM's

Diagnostic

Failure Description

RAM

Byte by byte test of RAM detects bad memory location

Flash (Program Memory)

8-bit Checksum of the entire Flash not zero.

Non-Volatile Memory

Byte by byte test of Non-Volatile Memory detects bad memory
location

Temperature Sensor

Temperature Sensor reports a value outside the designed range of

0° C to 100° C

Power Supply (Internal)

Any internally generated power supply voltage outside operational
limits. (3.3 Volt and 7.6 Volt internal supply voltages must be within
±5% of nominal value.)

Alarm

Severity

Alarm

Latching Contact Low

High

Delay

Code

Enable

Enable

Limit

Limit

Diagnostic

Alarm

12

n/a

Off

n/a

n/a

n/a

Flow 1

Off

11

Off

Off

0%

120%

1.0

Flow 2

Off

10

Off

Off

0%

120%

1.0

No Flow Indication

Alarm

9

Off

Off

2%

n/a

1.0

Setpoint Deviation

Alarm

8

Off

Off

-10%

+10%

1.0

Totalizer Overflow

Off

7

n/a

Off

n/a

n/a

n/a

User Power Supply

Alarm

6

Off

Off

13.5

27.0

1.0

Setpoint Input Out of Range

Alarm

5

Off

Off

n/a

n/a

1.0

Flow Output Out of Range

Alarm

4

Off

Off

n/a

n/a

1.0

Flow Output Loop Open

Off

3

Off

Off

n/a

n/a

1.0

Flow Sensor Out of Range

Alarm

1

Off

Off

n/a

n/a

1.0

Alarm Summary
The following table summarizes the parameters for each alarm type and
the respective default values.

3-6-2 Diagnostic Alarms (Analog versions only)

A Diagnostic Alarm will be indicated when any of the diagnostics below
detect a failure providing a visual indication via the red and/or green LED,
and activating the TTL open collector output located on the 15 pin
D-Connector. The diagnostic test or tests that have detected a problem and
caused the Diagnostic Alarm to occur can be determined only by reading a
parameter via the Service Port. When a diagnostic alarm occurs, the
device will automatically reset after approximately 5 seconds.