Installation

procedure for control function a

→

Pressurize lower control air connection with compressed air
(value as indicated on the type label) (see

“Fig. 29: Control air

connection”).

→

Place actuator on the body.

→

Lightly cross-tighten the body screws until the diaphragm is
between the body and actuator.
do not tighten the screws yet.

→

Actuate the diaphragm valve twice to position the diaphragm
correctly.

→

Without applying pressure, tighten the body screws to the per-
mitted tightening torque (see “Tab. 9: Tightening torques for
diaphragms”)
.

→

Pressurize lower control air connection with compressed air (value
as indicated on the type label).

→

Check the tightening torque of the screws again.

procedure for actuator with control functions B and i:

→

Place actuator on the body.

→

Lightly cross-tighten the body screws without pressurization until
the diaphragm is between the body and actuator.
do not tighten the screws yet.

→

Pressurize upper control air connection with compressed air (value
as indicated on the type label) (see below “Fig. 29: Control air
connection”
).

→

Actuate the diaphragm valve twice.

→

Tighten the body screws to the permitted tightening torque (see
“Tab. 9: Tightening torques for diaphragms”).

Lower control air connection
(for CFA and CFI)

Upper control air connection
(for CFB and CFI)

Fig. 29: Control air connection

Orifice

(Diaphragm size)

[mm]

tightening torques for diaphragms [nm]

epdm / fkm

ptfe / advanced ptfe /

laminated advanced ptfe

8

2

2.5

15

3.5

4

20

4

4.5

25

5

6

32

6

8

40

8

10

50

12

15

65

20

30

Tab. 9: Tightening torques for diaphragms

english

Type 2030, 2031, 2031 K, 2032,

2033, 2037