12 malfunctions, 13 spare parts – Burkert Type 2037 User Manual

Page 33

Advertising
background image

33

Malfunctions

12

malfuncTiOns

malfunction

cause / remedial action

Actuator
does not
switch

Control connection interchanged *
CFA

Connect lower control connection

CFB

Connect upper control connection

CFI

Upper control connection: Close
Lower control connection: Open

* see “Fig. 32: Control air connection”

Control pressure too low

See pressure specifications on the type label.

Medium pressure too high

See pressure specifications on the type label.

Valve is not
sealed

Medium pressure too high

See pressure specifications on the type label.

Control pressure too low

See pressure specifications on the type label.

Flow rate
reduced

PTFE diaphragm bulging

Replace diaphragm.

13

spare parTs

Warning!

risk of injury when opening the actuator body!
The actuator contains a tensioned spring. If the body is opened,
there is a risk of injury from the spring jumping out!

▶ Carefully open the actuator body and hold it in such a way that any

parts which jump out cannot injure anyone or damage anything.

CauTion!

risk of injury and/or damage by the use of incorrect parts!
Incorrect accessories and unsuitable spare parts may cause injuries
and damage the device and the surrounding area.

▶ Use only original accessories and original spare parts from

Bürkert.

Types 2030, 2031, 2031 K, 2032 and 2033 are available as spare
parts for the piston-controlled diaphragm valves.
• Seal set,
• Diaphragm.