Fluid Components International ST100 Series User Manual

Page 8

Advertising
background image

GENERAL

ST100 Series Flow Meter

4

Fluid Components International LLC

1” to 36” [25 mm to 914 mm]

1” to 60” [25 mm to 1524 mm]

Fixed lengths from 2.6” to 60” [66 mm to 1524 mm]

„

ST100L In-line Flow Tube

Flow element is threaded and keyed in an in-line flow tube, calibrat-

ed and supplied as a spool-piece; options include low flow injection

tubes and built-in Vortab flow conditioners for optimum low flow

rangeability and performance

Size: 1” diameter tubing; 1”, 1 1/2” or 2” schedule 40 pipe

Length: 9 nominal diameters

Process Connections: Female NPT, male NPT, ANSI or DIN

flanges, or butt weld prepared

Option: Flanges sized for flow tube

„

Remote Transmitter Configurations: Transmitter may be

mounted remotely from flow element using interconnecting cable

(up to 1000’ [300 m])

„

STP Models: Additional Specifications on Pressure Sensor

Calibrated at nominal 70 °F [21 °C]

Zero/Span Shift: 0.83% full scale/100 °F [1.5% full scale/100 °C]

Zero Tolerance: ± 0.5% of full scale

Span Tolerance: ± 0.5% of full scale

Long Term Stability: ± 0.2% full scale per year
Maximum over Pressure:

50 psi, 100 psi [3,4 bar, 7 bar] versions 3.0 x rated rate range

500 psi, 1000 psi [34 bar, 70 bar] versions 2.0 x rated rate range
Minimum burst Pressure (all):

50 psi, 100 psi [3,4 bar, 7 bar] versions 40 x rated rate range

500 psi, 1000 psi [34 bar, 70 bar] versions 20 x rated rate range
Wetted Materials:

17-4 PH stainless steel diaphragm (not recommended for hydrogen

service; contact FCI for Model STP for use in hydrogen)
304 stainless steel fittings

Flow Transmitter/Electronics

„

Operating Temperature: 0 °F to 140 °F [-18 ° to 60 °C]

„

Input Power

AC: 85 Vac to 265 Vac, 50 Hz to 60 Hz

DC: 24 Vdc ± 20%

„

Power Consumption

AC: 85 to 265V = 10W, 1 Flow Element

13.1W, 2 Flow Element

DC: 24V = 9.6W, 1 Flow Element

13.2W, 2 Flow Elements

„

Outputs

Analog

Standard: Three (3) 4-20 mA*, 0-1kHz, or 0-10 kHz pulse/frequency
4-20 mA outputs are user assignable to flow rate, temperature

and/or if so equipped, pressure; outputs are user programmable to

full flow range or subsets of full flow range; pulse/frequency output

is user selectable as pulse for external counter/flow totalizer, or as

0-1 kHz or 0-10 kHz frequency representing flow rate
* Outputs are isolated and have fault indication per NAMUR NE43

guidelines, user selectable for high (>21.0 mA) or low (<3.6 mA)
Optional: Standard output plus two (2) 2A SPDT relays

Relays independently user assignable to flow, temperature or

pressure; user programmable for hi/lo trip, hysteresis from 00.0 to

99.9 counts and time delay from 00.0 to 99.9 seconds
Digital

Standard: USB, Ethernet

Optional: HART (comes standard with analog outputs, V7 compliant

F

oundation

fieldbus H1, PROFIBUS PA or Modbus RS-485

„

Auxiliary Inputs

Two 4-20 mA input channels; used for FCI administered special

configurations to allow ST100 Series to accept inputs from external

devices such as gas analyzers, gas composition or pressure sensors

„

Enclosures

Main Transmitter / Electronics:

NEMA 4X, IP67; polyester powder coated aluminum; 4 conduit ports

threaded as 1/2” NPT or M20x1.5; 7.74” x 5.40” x 5.00” [196.6 mm x

137.2 mm x 127 mm]; stainless steel enclosure pending

Local Enclosure (Remote Configuration):

Model ST100L, Models ST100 and ST102 without packing gland

option:

NEMA 4X, IP67; polyester powder coated aluminum; 2 conduit ports

threaded as 1/2” NPT or M20x1.5; 3.75” x 4.00” x 3.24” [95 mm x

102 mm

x 82 mm]

Models ST100 and ST102 with medium pressure packing gland

option; ST110, ST112 and all STP Models:

NEMA 4X, IP67; polyester powder coated aluminum; 1 conduit port

threaded as 1” NPT or M20x1.5; 5.40” x 4.82” [137.2 mm x 122 mm]

„

Data Logger

User programmable for readings per time increment to a maximum

of 1 reading/second; removable, circuit board-mountable

2GB micro-SD (secure digital) memory card supplied; stores

approximately 21M readings in ASCII comma-separated format

„

Readout/Display and optical Touch buttons (optional):

• Large 2” x 2” [50 mm x 50 mm] LCD; digital plus bar graph and

engineering units

• Digital displays of flow rate, total flow, temperature and pressure

(with STP models); user selectable for engineering units

• Analog bar graph of flow rate

• Relay/alarm status indication

• User programmable 17 alphanumeric character field associated

with each calibration group

• Set-Up & Service mode displays text and service codes

• Four (4) optical touch buttons for user programming of instrument

set-up and service interrogation

• Optical touch button activation through front window – no need to

open enclosure to access or activate

• Display is electronically rotatable in 90° increments to optimize

viewing angle

Note: If readout/display not ordered, all user set-up and service inter-

rogation must be done via computer link to bus comm and/or USB

port.