Installation – Hach-Lange RTC103 N-Module User Manual

Page 17

Advertising
background image

17

Installation

1-Channel RTC103 N-Module

Module

Name

Terminal Signal

Channel

Function

2 fold digital output

1

KL2032

1

+24 V/0 V

Input Signals ok (24V), Input signal faulty (0V)

5

+24 V/0 V

RTC operating (24V), RTC failure (0V)

1 fold analog output

KL4011 1 - 3

0/4 to 20 mA

Output DO set point

1 fold analog intput

KL3011 1 - 2

0/4 to 20 mA

Flow rate aeration lane

1 fold analog input

KL3011 1 - 2

0/4 to 20 mA

Flow rate internal recirculation or return sludge

Bus termination

KL9010

Bus termination

1

Ground Connector 3 and 7, 24 V Connector 6.

2-Channel RTC103 N-Module

Module

Name

Terminal Signal

Channel

Function

4 fold digital output

1

KL2134

1

+24 V/0 V

1

Input Signals ok (24V), Input signal faulty (0V)

5

+24 V/0 V

1

RTC operating (24V), RTC failure (0V)

4

+24 V/0 V

2

Input Signals ok (24V), Input signal faulty (0V)

8

+24 V/0 V

2

RTC operating (24V), RTC failure (0V)

2 fold analog output

KL4012

1 - 3

0/4 to 20 mA

1

Output DO set point lane 1

5 - 7

0/4 to 20 mA

2

Output DO set point lane 2

1 fold analog intput

KL3011 1 - 2

0/4 to 20 mA

1

Flow rate aeration lane 1

1 fold analog input

KL3011 1 - 2

0/4 to 20 mA

2

Flow rate internal recirculation or return sludge
lane 1

1 fold analog intput

KL3011 1 - 2

0/4 to 20 mA

1

Flow rate aeration lane 2

1 fold analog input

KL3011 1 - 2

0/4 to 20 mA

2

Flow rate internal recirculation or return sludge
lane 2

Bus termination

KL9010

Bus termination

1

Ground Connector 3 and 7, 24 V Connector 6.

1-Channel RTC103 N-Module DO aeration stages control

Module

Name

Terminal Signal

Channel

Function

8 fold digital output

1

KL2408

1

+24 V/0 V

Input Signals ok (24V), Input signal faulty (0V)

2

+24 V/0 V

Aeration step 1 ON / OFF

3

+24 V/0 V

Aeration step 2 ON / OFF

4

+24 V/0 V

Aeration step 3 ON / OFF

5

+24 V/0 V

Aeration step 4 ON / OFF

6

+24 V/0 V

Aeration step 5 ON / OFF

7

+24 V/0 V

Aeration step 6 ON / OFF

8

+24 V/0 V

RTC operating (24V), RTC failure (0V)

1 fold analog output

KL4011 1 - 3

0/4 to 20 mA

Output DO set point

1 fold analog intput

KL3011 1 - 2

0/4 to 20 mA

Flow rate aeration lane

1 fold analog input

KL3011 1 - 2

0/4 to 20 mA

Flow rate internal recirculation or return sludge

Bus termination

KL9010

Bus termination

1

Ground Connector 3 and 7, 24 V Connector 6.

Advertising