Parameterization and operation

MODEL CORRECTION FACT.

This factor can be used on order to fine tune the DO concentration
calculated by the model (feed forward part of the N-RTC).

SUBSTIT. DO FOR MODEL

If there is a failure in any of the input signals (NH4-N, TSS, Flow) the
N-RTC will apply the this DO feed forward set point for all further
calculation

[mg/L]

NH4-N SETPOINT

Desired set point of the NH4-N concentration effluent aeration

[mg/L]

P FACT NH4

Note: These settings are only necessary if NH

4

-N measurement in

effluent for feed back control is available!

Proportional factor for the PID closed loop controller for the NH4-N
concentration effluent aeration.

[1/mg/L]

INTEGRAL TIME NH4

Note: These settings are only necessary if NH

4

-N measurement in

effluent for feed back control is available!

Integral time for the PID closed loop controller for the NH4-N
concentration in the thickened sludge.

Note: INTEGRAL TIME NH4 is set to “0” to deactivate the integral
part of the PID controller.

[min]

DERIVATIVE TIME NH4

Note: These settings are only necessary if NH

4

-N measurement in

effluent for feed back control is available!

Derivation time for the PID closed loop controller for the NH

4

-N

concentration effluent aeration

Note: DERIVATIVE TIME NH4 is set to “0” to deactivate the
derivative part of the PID controller.

[min]

LIMITS

MIN DO

If a calculated DO set point is lower than the MIN DO value, the DO
set point is set to that value

[mg/L]

MAX DO

If a calculated DO set point is higher than the MIN DO value, the DO
set point is set to that value

[mg/L]

SMOOTHING

Smoothing on the calculated DO set point

[min]

DO CONTROL

CHANNEL 1

DERIVATIVE TIME

Derivative Time of DO controller

[min]

DAMPING

Damping of DO control

[min]

SUBST AERATION

If the DO sensor (e.g. LDO) signals a fault, the set aeration stage is
selected

[Stage]

NO. OF STAGES

Number of controlled aeration stages (maximun 6)

[Stage]

VFD P MIN

fixed to 100%

[%]

CHANNEL 2

same as CHANNEL 1

4.5.2

2-Channel RTC103 N-Module Stages (Continued)

RTC MODULES / PROGNOSYS

RTC MODULES