Parameterization and operation

MODEL CORRECTION FACT.

This factor can be used to fine tune the DO concentration calculated
by the model (feed forward part of the N-RTC).

SUBSTIT. DO FOR MODEL

If there is a failure in any of the input signals (NH4-N, TSS, Flow) the
N-RTC will apply this DO feed forward set point for all further
calculations.

[mg/L]

NH4-N SETPOINT

Desired set point of the NH4-N concentration effluent aeration

[mg/L]

P FACT NH4

Note: These settings are only necessary if NH

4

-N measurement in

effluent for feed back control is available!

Proportional factor for the PID closed loop controller for the NH4-N
concentration effluent aeration.

[1/mg/L]

INTEGRAL TIME NH4

Note: These settings are only necessary if NH

4

-N measurement in

effluent for feed back control is available!

Integral time for the PID closed loop controller for the NH4-N
concentration in the thickened sludge.

Note: INTEGRAL TIME NH4 is set to “0” to deactivate the integral
part of the PID controller.

[min]

DERIVATIVE TIME NH4

Note: These settings are only necessary if NH

4

-N measurement in

effluent for feed back control is available!

Derivation time for the PID closed loop controller for the NH

4

-N

concentration effluent aeration

Note: DERIVATIVE TIME NH4 is set to “0” to deactivate the
derivative part of the PID controller.

[min]

LIMITS

MIN DO

If a calculated DO set point is lower than the MIN DO value, the DO
set point is set to that value

[mg/L]

MAX DO

If a calculated DO set point is higher than the MIN DO value, the DO
set point is set to that value

[mg/L]

SMOOTHING

Smoothing on the calculated DO set point

[min]

INPUTS

CHANNEL 1

MIN INFLOW

Minimum flow rate of influent according to measurement signal
corresponding to 0/4mA

[L/s]

MAX INFLOW

Maximum flow rate of influent according to measurement signal
corresponding to 20mA

[L/s]

0/4 to 20 mA

Transfer range of 0/4 to 20 mA current loop as set in connected flow
measuring instrument.