Parameterization and operation

Q RETURN RATIO

Note: 0/4 to20 mA input can be used either for Qreci or for Qras.

If the value Q RETURN RATIO is “0” the RAS flow is calculated
bases on the mA input signal.
If the value is different from “0” the RAS flow is calculated from the
inflow:
Q RETURN = Q RETURN RATIO * INFLOW
within the limits of MIN RETURN SLUDGE and MAX RETURN
SLUDGE.

[%]

CHANNEL 2

same as CHANNEL 1

OUTPUTS

CHANNEL 1

0/4 to 20 mA

Analog outputs to control VFD blowers.
Transfer range of 0/4 to 20 mA current loop

CHANNEL 2

same as CHANNEL 1

VOLUME

CHANNEL 1

VOLUME

Aerated volume

[m

3

]

CHANNEL 2

MODBUS

ADDRESS

Start address of an RTC within the MODBUS network.

DATA ORDER

Specifies the register order within a double word. Presetting:
NORMAL

DATALOG INTRVAL

Indicates the interval in which the data is saved in the log file.

[min]

PROGNOSYS

Activate or deactivate PROGNOSYS for RTC control. "Activate"
means if Measurement Indicator from relevant sensor decrease to
50% or lower RTC control do not use this measurement and switch
to adequate fall back strategy.

SET DEFAULTS

Restores the factory settings.

MAINTENANCE

RTC DATA

RTC MEASUREMEN

Specifies the value measured by the RTC, e. g. the influent
measurement.

RTC ACTUAT VAR

Specifies the variable calculated by the RTC, e. g. whether the
aeration should be switched on or off.

DIAG/TEST

EEPROM

Hardware test

RTC COMM TO

Communication time-out

RTC CRC

Communication check sum

MODBUS ADDRESS

Here, the address is displayed where the communication actually
takes place. Presetting: 41

LOCATION

Here, a location name can be assigned for better identification of the
RTC module, e.g. activation 2.

4.5.3

2-Channel RTC103 N-Module VFD (Continued)

RTC MODULES / PROGNOSYS

RTC MODULES

RTC