15 displayed measurement values and variables, Parameterization and operation – Hach-Lange RTC103 N-Module User Manual

Page 52

Advertising
background image

52

Parameterization and operation

4.15 Displayed measurement values and variables

The following measurement values and variables are shown on
the SC1000 display and transferred via fieldbus.

Parameter Unit

Description

Note

RTC103 N-Module, 1-channel

MEASUREMEN 1

Qin 1

L/s

Flow rate aeration lane

MEASUREMEN 2

Qrec 1

L/s

Flow rate internal recirculation or return
sludge

ACTUAT VAR 3

NffO 1

mg/L

DO demand calculated for influent
NH

4

-N load

ACTUAT VAR 4

NfbO 1

mg/L

Additional DO demand calculated from
NH

4

-N effluent concentration

always 0 if no effluent NH

4

-N

measurement available

ACTUAT VAR 5

Osetp 1

mg/L

DO Setpoint calculated from sum NffO
+ NfbO

ACTUAT VAR 6

Oreg 1

Internal calculation value for DO
control

always 0 if RTC103 N without DO
control

ACTUAT VAR 7

B_S 1

Stage

Aeration stage (B_S1)

always 0 if RTC103 N without DO
control

ACTUAT VAR 8

A_S 1

%

Aeration VFD (A_S 1)

always 0 if RTC103 N without DO
control

RTC103 N-Module, 2-channel

MEASUREMEN 1

Qin 1

L/s

Flow rate aeration lane 1

MEASUREMEN 2

Qrec 1

L/s

Flow rate internal recirculation or return
sludge lane 1

MEASUREMEN 3

Qin 2

L/s

Flow rate aeration lane 2

MEASUREMEN 4

Qrec 2

L/s

Flow rate internal recirculation or return
sludge lane 2

ACTUAT VAR 5

NffO 1

mg/L

DO demand calc.from influent
load(NffO 1)

ACTUAT VAR 6

NfbO 1

mg/L

Additional DO demand calculated from
NH

4

-N effluent concentration

always 0 if no effluent NH

4

-N

measurement available

ACTUAT VAR 7

Osetp 1

mg/L

DO Setpoint (Osetp1)

ACTUAT VAR 8

Oreg 1

Internal calculation value Oreg1

always 0 if RTC103 N without DO
control

ACTUAT VAR 9

B_S 1

Aeration stage (B_S1)

always 0 if RTC103 N without DO
control

ACTUAT VAR 10

A_S 1

Aeration VFD (A_S 1)

always 0 if RTC103 N without DO
control

ACTUAT VAR 11

NffO 2

mg/L

DO demand calc.from influent load
(NffO 2)

ACTUAT VAR 12

NfbO 2

mg/L

Additional DO demand calculated from
NH

4

-N effluent concentration

always 0 if no effluent NH

4

-N

measurement available

ACTUAT VAR 13

Osetp 2

mg/L

DO Setpoint (Osetp2)

ACTUAT VAR 14

Oreg 2

Internal calculation value Oreg2

always 0 if RTC103 N without DO
control

ACTUAT VAR 15

B_S 2

Stage

Aeration stage (B_S2)

always 0 if RTC103 N without DO
control

ACTUAT VAR 16

A_S 2

%

Aeration VFD (A_S 2)

always 0 if RTC103 N without DO
control