Installation – Hach-Lange RTC103 N-Module User Manual

Page 19

Advertising
background image

19

Installation

2-Channel RTC103 N-Module connectors DO aeration stages / analog control

Module

Name

Terminal Signal

Channel

Function

16 fold digital output

1

KL2809

1

+24 V/0 V

1

Input Signals ok (24V), Input signal faulty (0V)

2

+24 V/0 V

1

Aeration step 1 ON / OFF (VFD)

3

+24 V/0 V

1

Aeration step 2 ON / OFF (VFD)

4

+24 V/0 V

1

Aeration step 3 ON / OFF

5

+24 V/0 V

1

Aeration step 4 ON / OFF

6

+24 V/0 V

1

Aeration step 5 ON / OFF

7

+24 V/0 V

1

Aeration step 6 ON / OFF

8

+24 V/0 V

1

RTC Channel 1 operating (24V), RTC failure (0V)

9

+24 V/0 V

2

Input Signals ok (24V), Input signal faulty (0V)

10

+24 V/0 V

2

Aeration step 1 ON / OFF (VFD)

11

+24 V/0 V

2

Aeration step 2 ON / OFF (VFD)

12

+24 V/0 V

2

Aeration step 3 ON / OFF

13

+24 V/0 V

2

Aeration step 4 ON / OFF

14

+24 V/0 V

2

Aeration step 5 ON / OFF

15

+24 V/0 V

2

Aeration step 6 ON / OFF

16

+24 V/0 V

2

RTC Channel 2 operating (24V), RTC failure (0V)

2 fold analog output

KL4012

0/4 to 20 mA

1

Output 1 VFD for DO control

0/4 to 20 mA

1

Output 2 VFD for DO control

2 fold analog output

KL4012

0/4 to 20 mA

2

Output 1 VFD for DO control

0/4 to 20 mA

2

Output 2 VFD for DO control

1 fold analog intput

KL3011 1 - 2

0/4 to 20 mA

1

Flow rate aeration lane

1 fold analog input

KL3011 1 - 2

0/4 to 20 mA

1

Flow rate internal recirculation

1 fold analog intput

KL3011 1 - 2

0/4 to 20 mA

2

Flow rate aeration lane

1 fold analog input

KL3011 1 - 2

0/4 to 20 mA

2

Flow rate internal recirculation

Bus termination

KL9010

Bus termination

1

Ground Connector 3 and 7, 24 V Connector 6.

Advertising