Technical data – Hach-Lange RTC103 N-Module User Manual

Page 8

Advertising
background image

8

Technical data

Analog output

Outputs for DO setpoint or VFD control

Number of outputs

One-channel: 1 (KL4011); 1 (KL4012) VFD control

Two-channel: 1 (KL4012); 2 (KL4012) VFD control

Supply voltage

24 V DC via the power contacts
(Alternatively, 15 V DC with bus termination KL9515)

Signal current

0/4 to 20 mA

Working resistance

< 500 Ohm

Measurement error

± 0.5 LSB linearity error
± 0.5 LSB offset error
± 0.5 % (relative to the measuring range end value)

Resolution

12 bit

Conversion time

Approximately 1.5 ms

Electrical isolation

500 V

eff

(K-bus/field voltage)

Environmental conditions

Working temperature

0 to 50 °C (32 to 122 °F)

Storage temperature

–25 to +85 °C (–13 to 185 °F)

Relative humidity

95 %, non-condensing

Miscellaneous

Pollution degree
Protection class
Installation category
Maximum altitude

3
III
I
2000 m (6.562 ft.)

Degree of protection

IP20

Installation

DIN rail EN 50022 35 × 15

1