Parameterization and operation

4.11.8 MIN RETURN SLUDGE

Minimum return sludge flow rate according to measurement
signal corresponding to 0/4mA.

4.11.9 MAX RETURN SLUDGE

Maximum return sludge flow rate of influent according to
measurement signal corresponding to 20mA.

4.11.10 0/4 to 20mA

Transfer range of 0/4 to 20mA current loop as set in connected
flow measuring instrument.

4.11.11 Q RETURN RATIO

If the value Q RETURN RATIO is “0” the RAS flow is calculated
bases on the mA input signal. If the value is different from “0” the
RAS flow is calculated from the inflow:

Q RETURN = Q RETURN RATIO * INFLOW

within the limits of MIN RETURN SLUDGE and MAX RETURN
SLUDGE.

4.12 OUTPUTS

4.12.1 MIN DO SETTING (only for option without DO control)

Minimum DO set point corresponding to 0/4mA.

4.12.2 MAX DO SETTING (only for option without DO control)

Maximum DO set point corresponding to 20mA.

4.12.3 0/4 to 20mA

Transfer range of 0/4 to 20mA current loop

without DO control: for DO setpoint signal.

with VFD DO control: for VFD blowers signal.

4.13 Volume

4.13.1 Aerated volume

Size of aerated basin (or zone) in m

3

.

4.14 MODBUS

4.14.1 ADDRESS

Start address of an RTC within the modbus network.

4.14.2 DATAORDER

Specifies the register order within a double word.

Presetting: NORMAL