Parameterization and operation

P FACT NH4

Note: These settings are only necessary if NH

4

-N measurement in

effluent for feed back control is available!

Proportional factor for the PID closed loop controller for the NH4-N
concentration effluent aeration.

[1/mg/L]

INTEGRAL TIME NH4

Note: These settings are only necessary if NH

4

-N measurement in

effluent for feed back control is available!

Integral time for the PID closed loop controller for the NH4-N
concentration in the thickened sludge.

Note: INTEGRAL TIME NH4 is set to “0” to deactivate the integral
part of the PID controller.

[min]

DERIVATIVE TIME NH4

Note: These settings are only necessary if NH

4

-N measurement in

effluent for feed back control is available!

Derivation time for the PID closed loop controller for the NH

4

-N

concentration effluent aeration

Note: DERIVATIVE TIME NH4 is set to “0” to deactivate the
derivative part of the PID controller.

[min]

LIMITS

MIN DO

If a calculated DO set point is lower than the MIN DO value, the DO
set point is set to that value

[mg/L]

MAX DO

If a calculated DO set point is higher than the MIN DO value, the DO
set point is set to that value

[mg/L]

SMOOTHING

Smoothing on the calculated DO set point

[min]

DO CONTROLL

P GAIN DO

Proportional factor for the PD closed loop controller for the DO
concentrtion in the aeration.

[1/mg/L]

DERIVATIVE TIME

Derivative Time of DO controller

[min]

INT PART

Integral part for DO control

DAMPING

Damping of DO control

[min]

SUBST AERATION

If the DO sensor (e.g. LDO) signals a fault, the set aeration stage is
selected

[Stage]

NO. OF STAGES

Number of controlled aeration stages (maximun 6)

[Stage]

VFD P MIN

Set minimum speed for VFD controlled blowers (stage 1 and 2)

[%]

INPUTS

MIN INFLOW

Minimum flow rate of influent according to measurement signal
corresponding to 0/4mA

[L/s]

MAX INFLOW

Maximum flow rate of influent according to measurement signal
corresponding to 20mA

[L/s]

0/4 to 20 mA

Transfer range of 0/4 to 20 mA current loop as set in connected flow
measuring instrument.

4.4.3

1-Channel RTC103 N-Module VFD (Continued)