Operating instructions, Recovery procedures warning – Robinair 178012K Recovery, Recycling, Recharging Unit User Manual

Page 12

Advertising
background image

© 2000 Robinair, SPX Corporation

10

Operating Instructions

Diagram of Control Panel

Low Side
Gauge

High Side
Gauge

High
Side
Valve

Liquid/Vapor
Indicator

Display

Main

Power

Switch

Air

Purge

Valve

Keypad

Low

Side

Valve

Air Purge Gauge

RECOVERY PROCEDURES

WARNING!

Always wear safety goggles when working with refrigerant. Use only
authorized refillable refrigerant tanks. Disconnect hoses with extreme
caution!

All hoses may contain refrigerant under pressure. Read and follow all
warnings at the beginning of this manual before operating the unit.

Before beginning recovery, be sure your unit is set up as described in the Set-Up
Instructions
. Also be sure there is vacuum pump oil in the vacuum pump.

1. Connect the high and low side hoses to the A/C-R system, as you would normally

connect your manifold gauge set.

2. Be sure both the high and low side valves on the control panel are open. Also be

sure both valves on the tank are open.

3. Plug the unit into the proper voltage outlet, and turn on the MAIN POWER

switch. The display shows either “134a” (which indicates R-134a automotive
refrigerant that uses

1

/

2

” Acme fittings) or “R12” (which indicates all other refriger-

ant types that use

1

/

4

” flare fittings).

4. Press SHIFT/RESET, then press RECOVER.