Operating instructions, Important, First – Robinair 178012K Recovery, Recycling, Recharging Unit User Manual

Page 14: Changing refrigerant types

Advertising
background image

© 2000 Robinair, SPX Corporation

12

Operating Instructions

INST0146

Diagram of Unit’s Components — External View

Scale Assembly

Lockout Box

High Side Port

Low Side Port

Red Vapor Hose

Blue Liquid Hose

Yellow Air
Purge Hose

Tank Vapor Valve

Tank Liquid Valve

Air Purge Fitting

50 lb. (23 kg)
Unit Tank

Important!

Before changing
refrigerant types,
be sure the red
high side and
blue low side
hoses are dis-
connected from
the A/C system.

CHANGING REFRIGERANT TYPES

1. Be sure the red high side and blue low side hoses are disconnected from the A/C

system, then open the manifold and tank valves.

2. Turn on unit and close the liquid valve on the tank. Press SHIFT/RESET until the

"program" message displays. Press and hold SHIFT/RESET and then press "1" to
recycle. Unit will pull into a vacuum and shut off.

3. Turn unit on and press SHIFT/RESET until the “Clr” message appears.

4. Press HOLD/CONT to start the system oil separator clearing process.

During the system oil separator clearing process, the compressor is activated and
the “OIL” message displays. The compressor will stop while the unit equalizes
pressure and the “OIL” message will continue to display. When the unit reaches the
correct pressure, the display alternately flashes the messages “OIL” and “DRN.”
Open the system oil drain valve to drain the oil. After all oil has drained, the

First!

Perform
"RECOVERY
PROCEDURES"
before starting
"CHANGING
REFRIGERANT
TYPES".