7. Error

T

reatment

108

Value in No.1053 63

Name

Vision System Detection Error

Description

Vision system could not detect the work.

Treatment

Confirm the work is within the image capturing range.
Confirm that the job set to detect the work is executed.
Confirm the vision system is online.
Confirm the lights are on if there are.
Confirm the lens cover on the camera is removed.

Value in No.1053 64

Name

Vision System Formula Creation Error

Description

Adjustment data could not be created since there was a problem in the data acquired
in the calibration.

Treatment

Confirm the movement amount setting (refer to Section 5.8.2, 5.8.3 [Procedure 8] (5))
is evenly allocated within the image capturing range and retry the calibration.
If the same error occurs again, please contact us.

Value in No.1053 65

Name

Vision System Error Code Failure Error

Description

There is an error in the returned value from the vision system.

Treatment

Turn OFF the power to the vision system and reboot.
If the same error occurs again, please contact us.