7. Error
T
reatment
108
Value in No.1053 63
Name
Vision System Detection Error
Description
Vision system could not detect the work.
Treatment
Confirm the work is within the image capturing range.
Confirm that the job set to detect the work is executed.
Confirm the vision system is online.
Confirm the lights are on if there are.
Confirm the lens cover on the camera is removed.
Value in No.1053 64
Name
Vision System Formula Creation Error
Description
Adjustment data could not be created since there was a problem in the data acquired
in the calibration.
Treatment
Confirm the movement amount setting (refer to Section 5.8.2, 5.8.3 [Procedure 8] (5))
is evenly allocated within the image capturing range and retry the calibration.
If the same error occurs again, please contact us.
Value in No.1053 65
Name
Vision System Error Code Failure Error
Description
There is an error in the returned value from the vision system.
Treatment
Turn OFF the power to the vision system and reboot.
If the same error occurs again, please contact us.