7. Error

T

reatment

109

7.3

Return Code List in READ Command (SEL Language)

Execution

If an error is occurred during the READ Command, the return code is stored to the Calibration

Process Status Monitor No.1055.

The return codes are listed below. Check the detail to take an appropriate counteraction.

Return

Code

Description and Treatment

0

READ Command completed in normal condition

1

Reception Time Out

The timeout duration is determined in TMRD or TMRW Command.

The reception will continue even though the return code is not returned.

2

Reception Timer Cancel

The condition in waiting is cancelled in the timer duration determined in TMRD or TMRW

Command.

3

Reception Overrun

The process of sending data was not made in time. Increase the process time by such way as

reducing the communication speed.

4

Framing Error or Parity Error

Framing Error : Data other than the specified format was received. Check the settings of

such parameters as parity and data bit length. If the problem cannot be

solved, also consider the influence of noise. Check the cable wires and their

shield treatment.

Parity Error : There was an error in the sent data.

Influence of noise can be considered. Check the cable wires and their shield

treatment.

5

Read Factor Error

The communication circuit was compulsorily shut down. Reboot the XSEL power.

Please contact us if the problem is not solved with this action.

6

Lead Task Complete

Program stopped while READ Command was executed.

7

Receive Error

There was an error in the receiving process for some reason.

Reboot the XSEL power.

Please contact us if the problem is not solved with this action.

8
9

10

11

12

These numbers are not in use.

13
14
15
16
17
18
19
20

Ethernet Related Error

Close the circuit once and reopen it.

Please contact us if the problem is not solved with this action.

21

Temporary QUE Overflow

An overflow was occurred in the communication circuit memory. Reboot the XSEL power.

Please contact us if the problem is not solved with this action.

22

Receive QUE Overflow

An overflow was occurred in the received data storage area.

Try to reduce the communication speed.

50 to

Please contact us.