Timing chart (Logic 8)

Safety input : X0

Safety output 1 :
Y0,Y1

Monitor output for
X0 and X1 : Y4

Monitor output for
safety output 1 :
Y12

Solenoid output:
Y17

Power ON

Off delay

time

(X4, X5, X10, X11 are ON in this chart.)

Safety input : X2

Safety input : X6

Control start input
: X12

Safety output 2 :
Y2,Y3

Monitor output for
safety output 2 :
Y13

Solenoid output:
Y20

Safety output 1

ON

Safety output

all ON

Safety output

all ON

Manual start input
: X13

Monitor output for
X2 and X3 : Y5

Monitor output for
X6 and X7 : Y7

Off delay

time

Off delay

time

Safety output 2

ON

1. Example to use a manual start input (X13) which is not detected adhesion of the start switch on partial stop.

0.1s...5s

Max. 6s

Min 0.1s

Note 1: When the input time difference of the dual channel safety inputs is 0.5s or more, an input monitor error is detected.

Refer to the following "Logic functions" for details.

Note 2: Example to turn on a control start input (X12) before turning on a manual start input (X13).

Safety input : X1

(Note 1)

Safety input : X3

(Note 1)

Safety input : X7

(Note 1)

(Note 1)

(Note 1)

(Note 1)

Max. 0.1s

Max. 0.1s

Min. 0.1s

Safety output 2

ON

0.1s...5s

Min. 0.1s

Max. 0.1s

Max. 0.1s

Min 0.1s

(Note 2)

Initialization