5-39

Safety input : X0

Control start input
: X17

Safety output :
Y0,Y1,Y2,Y3

Monitor output for
X0 and X1 : Y4

Monitor output for
safety output :
Y12,Y13

Muting lamp
output : Y17

Power ON

Off delay time

Muting input : X2

(X4, X5, X10...X13 are ON and X6, X7 are OFF in this chart.)

RUN monitor :
Y16

(Note 1)

Note 1: When the safety inputs were turned OFF before the muting inputs were turned ON, the muting functions are not effective
and the safety outputs are not turned ON.

Muting start

Muting end

Muting start

Muting end

Note 2: When the muting inputs are turned ON while the safety inputs are ON, the muting functions are effective and the safety
outputs are turned ON upon initiation of the start input.

2.Example of using the control start input (X17)

Max. 6s

Safety output

ON

0.1s...5s

Safety output

ON

( Note 2)

(Note 3)

Safety input : X1

Note 3: When the input time difference at the dual channel solid state inputs (X0-X1 and X2-X3) is greater than 0.1s

input monitor error is detected.
When the input time difference at the dual channel direct opening inputs

(X4-X5, X6-X7, X10-X11, and X12-X13) is greater than

input monitor error is detected.
Refer to the following "Logic functions" for details.

Max. 0.1s

(Note 3)

(Note 3)

0.1s...5s

Max. 0.1s

Initialization

Muting input : X3

(Note 1)

(Note 4)

(Note 4)

Note 4: When the input time difference at the muting inputs (X2-X3, X6-X7) is greater than 3s an input monitor error is detected.
Refer to the following "Logic functions" for details.