Timing chart (logic 4) – IDEC FS1A Controller User Manual
Page 79

5-38
Timing chart (Logic 4)
Safety input : X0
Manual start input
: X16
Safety output :
Y0,Y1,Y2,Y3
Monitor output for
X0 and X1 : Y4
Monitor output for
safety output :
Y12,Y13
Muting lamp
output : Y17
Power ON
Off delay time
Muting input : X2
(X4, X5, X10...X13 are ON and X6, X7 are OFF in this chart.)
RUN monitor :
Y16
(Note 1)
Note 1: When the safety inputs were turned OFF before the muting inputs were turned ON, the muting functions are not effective
and the safety outputs are not turned ON.
Muting start
Muting end
Muting start
Muting end
Note 2: When the muting inputs are turned ON while the safety inputs are ON, the muting functions are effective and the safety
outputs are turned ON upon input of the start input.
1.Example of using the manual start input (X16)
Min. 0.1s
Max. 6s
Safety output
ON
Safety input : X1
(Note 3)
Note 3: When the input time difference at the dual channel solid state inputs (X0-X1, X4-X5) is greater than 0.1s
input monitor error is detected.
When the input time difference at the dual channel direct opening inputs
(X10-X11, X12-X13) is greater than 0.5s
input monitor error is detected.
Refer to the following "Logic functions" for details.
(Note 3)
Max. 0.1s
Safety output
ON
( Note 2)
(Note 3)
Min. 0.1s
Max. 0.1s
Initialization
Muting input : X3
(Note 1)
(Note 4)
(Note 4 )
Note 4: When the input time difference at the muting inputs (X2-X3, X6-X7) is greater than 3s input monitor error is detected.
Refer to the following "Logic functions" for details.