57 timing chart (logic 6) – IDEC FS1A Controller User Manual

Page 98

Advertising
background image

5-57

Timing chart (Logic 6)

Teach mode

Mode select input
: X0

Safety input:

X2

Monitor output for
X2 or X3 : Y5

Monitor output for
X0 and X1 : Y4

Monitor output for
X10 or X11 : Y10

Safety output :
Y0,Y1,Y2,Y3

Manual start input
: X16

Power ON

Safety output ON

Off delay

time

Mode select input
: X1

Min. 0.1s

Max. 6s

Monitor output for
safety output :
Y12,Y13

Solenoid output :
Y17,Y20

RUN monitor :
Y16

Safety input :
X10,X11

Safety output ON

Off delay

time

Control start input
: X17

0.1s...5s

(X4...X7, X12, X13 are ON in this chart.)

Safety output ON

Safety input:

X3

(Note 1)

Note 1: The input monitor error detection time is infinite in the dual channel dependent inputs (X2-X3).

When the input time difference at the dual channel direct opening inputs (X4-X5, X6-X7, X10-X11, and X12-X13)is 0.5s or more,

an input monitor error is detected.

Refer to the following “Logic function” for details.

Max. 0.1s

Max. 0.1s

(Note 1)

(Note 2)

Note 2: Example to turn on a control start input (X17) before turning on the manual start input (X16).

Min. 0.1s

Max. 0.1s