Monitor output specifications – IDEC FS1A Controller User Manual

Page 19

Advertising
background image

2-10

Monitor output specifications

Output type

Source output (N channel MOSFET)

Rated output voltage

Power supply voltage

Minimum output voltage

Power supply voltage - 2.0V

Number of outputs

11(Y4, Y5, Y6, Y7, Y10, Y11, Y12, Y13, Y14, Y15, Y16)

Point

20mA maximum

Maximum output current

total

220mA maximum

Leakage current

0.1mA maximum

Cable length

Note1

100m maximum (total wiring length per 1output)

Note1. For cables longer than 30m between SafetyOne and connected devices, use grounded
shielded cables to assure electromagnetic compatibility.

Monitor output equivalent circuit

Internal

circuit

Logic

circuit

Yn

V-

V+


The specifications of the monitor outputs changes depending on the Logic selected. See further
information in “Chapter 5 LOGIC”. The basic specifications are the same.

Warning

Do not use monitor outputs for safety related purposes. This may cause a loss of safety
functions in case of failure of the SafetyOne or peripherals.

Advertising