19 timing chart (logic 2) – IDEC FS1A Controller User Manual

Page 60

Advertising
background image

5-19

Timing chart (Logic 2)

Safety input : X0

Manual start input
: X16

Safety output :
Y0,Y1,Y2,Y3

Monitor output for
X0 and X1 : Y4

Monitor output for
safety output :
Y12,Y13

RUN monitor :
Y16

Solenoid output :
Y17,Y20

Power ON

Safety output ON

Off delay

time

Safety input : X1

(X2, X4 and X6 are OFF and X3, X5, X7 and
X10...X13 are ON in this timing chart.)

Safety input : X0

Control start input
: X17

Safety output :
Y0,Y1,Y2,Y3

Monitor output for
X0 and X1 : Y4

Monitor output for
safety output :
Y12,Y13

RUN monitor :
Y16

Solenoid output :
Y17,Y20

Power ON

Safety output ON

Off delay

time

Safety input : X1

Min. 0.1s

1.Case to use the manual start input (X16)

2.Case to use the control start input (X17)

0.1s...5s

Max. 6s

Max. 6s

(Note)

Note:

When the input time difference for the dual channel safety inputs is 0.5s or more, an input monitor error is detected.
Refer to the following "Logic functions" for details.

(Note)

Max. 0.1s

(Note)

Max. 0.1s

(Note )

(X2, X4 and X6 are OFF and X3, X5, X7 and
X10...X13 are ON in this timing chart.)

Initialization

Initialization