5-9

Timing chart (Logic 1)

Safety input : X0

Manual start input
: X16

Safety output :
Y0,Y1,Y2,Y3

Monitor output for
X0 and X1 : Y4

Monitor output for
safety output :
Y12,Y13

RUN monitor :
Y16

Solenoid output :
Y17,Y20

Power ON

Safety output ON

OFF delay

time

Safety input : X1

(X2...X13 are ON in this timing chart.)

Safety input : X0

Control start input
: X17

Safety output :
Y0,Y1,Y2,Y3

Monitor output for
X0 and X1 : Y4

Monitor output for
safety output :
Y12,Y13

RUN monitor :
Y16

Solenoid output :
Y17,Y20

Power ON

Safety output ON

OFF delay

time

Safety input : X1

1.Case to use the manual start input (X16)

2.Case to use the control start input (X17)

0.1s...5s

Min. 0.1s

Max. 6s

Initialization

Max. 6s

(Note)

Note:

When the input time difference at the dual channel safety inputs is 0.5s or more, the input monitor error is detected.
Refer to the following "Logic functions" for details.

(Note)

Max. 0.1s

Max. 0.1s

(Note )

(Note )

(X2...X13 are ON in this timing chart.)