Control start, Description of operation – IDEC FS1A Controller User Manual

Page 140

Advertising
background image

5-99

Control start

This function confirms operation of the connected start input device. As shown in Fig.5-26, this
function is comprised of a functional input (I

n

) and a functional output (O

n

).

The start input (I

n

) ON operation is monitored to determine whether it is performed within the

designated control time (0.1 s to 5 s).

Fig. 5-26 Control start circuit

Description of operation

The operation timing is described in Fig. 5-27.

Ⅰ

If the input turns ON within the designated control time (0.1 s to 5 s), the output turns ON until

the connected self-holding function or another trigger input turns ON. (The function output
turns OFF after the other trigger input turns ON.)

Ⅱ

If the input does not turn ON within the designated control time (0.1 s to 5 s) (If the function

input turns on before 0.1 s or after 5 s), the output does not turn ON.

I

n

O

n

Control time
:0.1s~5s

Ⅰ

Ⅱ

0.1s

5s

0.1s

5s

Control time
:0.1s~5s

ON

OFF

ON

OFF

Fig. 5-27 Operation timing of the control start function





I

n

O

n

Control

Start

Control