GP4000 Series Hardware Manual

119

Environmental Specifications

Air quality requirements

Do not operate or store the GP unit where chemicals evaporate, or where chemicals
are present in the air:

z

Corrosive chemicals: Acids, alkalines, liquids containing salt.

z

Flammable chemicals: Organic solvents.

DC Model

AC Model

Physical Envir

onment

Surrounding Air
Temperature

0...55 °C (32...131 °F)

Storage Temperature

-20...60 °C (-4...140 °F)

Surrounding Air and
Storage Humidity

10...90% RH (Non condensing, wet bulb temperature 39

°C [102.2 °F] or less)

Dust

0.1 mg/m

3

(10

-7

oz/ft

3

) or less (non-conductive levels)

Pollution Degree

For use in Pollution Degree 2 environment

Corrosive Gases

Free of corrosive gases

Atmospheric Pressure
(Operating Altitude)

800...1,114 hPa (2,000 m [6,561 ft] or lower)

Mechanical Envir

onment

Vibration Resistance

IEC/EN 61131-2 compliant
5...9 Hz Single amplitude 3.5 mm (0.14 in.)
9...150 Hz Fixed acceleration: 9.8 m/s

2

X, Y, Z directions for 10 cycles (approx.100 minute)

Concussion Resistance IEC/EN 61131-2 compliant

147 m/s

2

, X, Y, Z directions for 3 times

Electrical Envir

onment

Noise Immunity

Noise Voltage: 1,000 Vp-p
Pulse Width: 1 µs
Rise Time: 1 ns

Noise Voltage: 1,500 Vp-p
Pulse Width: 1 µs
Rise Time: 1 ns

Electrostatic Discharge
Immunity

Contact Discharge Method: 6 kV (IEC/EN 61000-4-2 Level
3)

CAUTION

INOPERATIVE EQUIPMENT

Do not allow water, liquids, metal, and wiring fragments to enter the panel case.

Failure to follow these instructions can result in injury or equipment damage.