Replacing the Primary Battery

Introduction

The replacement battery (sold separately) for the primary battery in the GP unit is
available from Pro-face.

NOTE: The GP-4200 Series and GP-4301TW are not equipped with a primary
battery.

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

z

Follow the procedures step by step to replace the battery correctly and safely.

z

Before replacing the battery, turn OFF the GP unit’s power.

Failure to follow these instructions will result in death or serious injury.

DANGER

EXPLOSION, FIRE, OR CHEMICAL HAZARD

z

Use only the replacement battery manufactured by Pro-face.

z

Do not cause a short circuit.

z

Recycle or properly dispose of used batteries.

Failure to follow these instructions will result in death or serious injury.

NOTICE

LOSS OF DATA

The primary battery is non-rechargeable, and is used for data backup of memory
and the internal clock. If the primary battery is depleted, the backup data is lost.
One month before the primary battery is completely depleted, a message will
appear to indicate it is time to replace the primary battery.

z

Replace the battery within one month after the message appears. Otherwise,
backup data may be lost.

z

Complete replacing the battery within ten minutes of shutting down the GP unit.

z

The primary battery replacement time (within a month after the message
appears) is only a guideline. When backup SRAM data and clock data is lost
after the message appears, Pro-face does not perform data recovery/retrieval.
Pro-face does not accept any responsibility for the loss of data.

z

Replace the primary battery regularly every five years after you purchase the
GP unit.

Failure to follow these instructions can result in equipment damage.