Specifications of serial interface com1, Danger, Notice – Proface GP4600R - 12.1 Standard HMIs with Rear Mounting Options" User Manual

Page 90: 96 5 1 (gp unit side)

Advertising
background image

Specifications

90

Specifications of Serial Interface COM1

Introduction

NOTE:

For instructions on how to connect to other devices, always refer to the “GP-

Pro EX Device/PLC Connection Manual”.
The serial port is not isolated. The SG (signal ground) and FG (frame ground)
terminals are connected inside the GP unit.

Serial Interface COM1

GP-4401T / GP-4401WW

: D-Sub 9 pin plug connector via an RS-232C cable.

NOTE:

*1

You can switch pin #9 between RI and VCC via software.

DANGER

ELECTRIC SHOCK

When using the SG terminal to connect an external device to the panel:

z

Verify that a short-circuit loop is not created when you set up the system.

z

Connect the #5 SG terminal to remote equipment when the host (PLC) unit is
not isolated. Connect the #5 SG terminal to a known reliable ground connection
to reduce the risk of damaging the circuit.

Failure to follow these instructions will result in death or serious injury.

Pin Connection

Pin
No.

RS-232C

Signal Name

Direction

Meaning

1

CD

Input

Carrier Detect

2

RD(RXD)

Input

Receive Data

3

SD(TXD)

Output

Send Data

4

ER(DTR)

Output

Data Terminal Ready

5

SG

-

Signal Ground

6

DR(DSR)

Input

Data Set Ready

7

RS(RTS)

Output

Request to Send

8

CS(CTS)

Input

Send possible

9

CI(RI)/VCC

Input/–

Called Status Display
+5V±5% Output 0.25A

*1

Shell

FG

Frame Ground (Common
with SG)

NOTICE

EQUIPMENT DAMAGE

Use only the rated current.

Failure to follow these instructions can result in equipment damage.

9

6

5

1

(GP unit side)

Advertising