Proface GP4600R - 12.1 Standard HMIs with Rear Mounting Options" User Manual

Page 231

Advertising
background image

GP4000 Series Hardware Manual

231

8

When you are installing the GP unit horizontally, hold the GP unit so that the
arrow pointing in the horizontal direction on the rear surface of the GP unit
points up as shown in the figure.

1) Figure of the GP unit's rear surface when attaching installation brackets at

the top and bottom surfaces of the GP unit

2) Figure of the GP unit's rear surface when attaching installation brackets on

either side of the GP unit

9

Insert the GP unit through the rear surface of the panel, pass the stud bolts
through the four installation bracket holes, and then tighten nuts on the stud
bolts to fix the GP unit in place. The tightening torque is 0.8 N•m to 1.0 N•m
(7.1 lb-in to 8.9 lb-in).