3

Slowly peel the protective sheet off of the GP unit's screen.
Note: Peeling off the protective sheet with excessive force may peel off the film
of the touch panel.

4

When the GP unit is shipped from the factory, installation brackets are fixed to
its top surface and bottom surface.
These installation brackets are fixed in positions that do not match the resin
boss type, so follow the procedure below to change the positions in which the
installation brackets are attached.

5

Orient the GP unit so that its screen faces down, and then place the GP unit on
a clean and level surface.

6

Use a Phillips head screwdriver to remove the two installation screws fixing the
one installation bracket in place on the top surface of the GP unit. In the same
manner, remove the one installation bracket from the bottom surface.

7

Attach the installation brackets to the top and bottom surfaces of the GP unit
or to the sides of the GP unit. In each case, attach the surface of the installation
bracket that has six open holes to the GP unit as shown. Use a Phillips head
screwdriver to fix in place two installation screws per installation bracket. The
tightening torque is 0.8 N•m (7.1 lb-in).

1) Use two installation screws to fix the bracket in place. (Use the two inner

holes.)

8

When you are installing the GP unit horizontally, hold the GP unit so that the
arrow pointing in the horizontal direction on the rear surface of the GP unit
points up as shown in the figure.

1) Figure of the GP unit's rear surface when attaching installation brackets at

the top and bottom surfaces of the GP unit

2) Figure of the GP unit's rear surface when attaching installation brackets on

either side of the GP unit

9

Insert the GP unit through the rear surface of the resin plate, pass the bosses
through the four installation bracket holes, and then tighten the screws to fix the
GP unit in place. We recommend that you use M4 screws. The tightening
torque is 0.8 N•m (7.1 lb-in).