Output 2 mechanical relay, form a, Output 2 solid-state relay, form a, Output 3 mechanical relay, form c – Watlow EZ-ZONE ST User Manual

Page 24: Output 4 mechanical relay, form a

Advertising
background image

Ó

Warning:

Use National Electric (NEC)

or other country-specific

standard wiring and safety

practices when wiring and

connecting this controller to

a power source and to elec-

trical sensors or peripheral

devices . Failure to do so may

result in damage to equip-

ment and property, and/or

injury or loss of life .

NOTE: To prevent ground

loops, isolation needs to be

maintained from input to out-

put when using switched DC

or analog process outputs .

CAUTION: Always mount the

controller with the heat-sink

fins aligned vertically .

NOTE: Terminals L4 and

A1 on the limit connector

are jumpered at the factory

to complete the contactor

circuit . Additional switches

may be wired in series to the

terminals .

Ó

WARNING: If high voltage is

applied to a low-voltage con-

troller, irreversible damage

will occur .

Watlow EZ-ZONE

®

ST

22

Chapter 2 Install and Wire

Quencharc Note:

Switching pilot duty inductive

loads (relay coils, solenoids,

etc .) with the mechanical

relay, solid state relay or

open collector output options

requires use of an R .C . sup-

pressor .

Output 2 Mechanical Relay, Form A

common

normally open

L2
K2

Slot B

• 5 A at 240VÅ (ac) or 30VÎ (dc)

maximum resistive load

• 20 mV at 24V minimum load
• 125 VA pilot duty @ 120/240VÅ

(ac), 25 VA at 24VÅ (ac)

• 100,000 cycles at rated load
• Output does not supply power.
• for use with ac or dc
See Quencharc note.
ST (H, D, J, C) _ - _ _ _ _ - _ _ _ _

L2

K2

Output 2 Solid-State Relay, Form A

common

normally open

L2
K2

Slot B

• 0.5 A at 20 to 264VÅ (ac) maxi-

mum resistive load

• 20 VA 120/240VÅ (ac) pilot duty
• opto-isolated, without contact

suppression

• maximum off state leakage of

105 microamperes

• Output does not supply power.
• Do not use on dc loads.
See Quencharc note.
ST (K, B, P, E) _ - _ _ _ _ - _ _ _ _

L2

K2

Output 3 Mechanical Relay, Form C

normally open

normally closed

common

L3
K3
J3

Slot A

• 5 A at 240VÅ (ac) or 30VÎ (dc)

maximum resistive load

• 20 mA at 24V minimum load
• 125 VA pilot duty at 120/240VÅ

(ac), 25 VA at 24VÅ (ac)

• 100,000 cycles at rated load
• Output does not supply power.
• for use with ac or dc
See Quencharc note.
ST _ L - _ _ _ _ - _ _ _ _ (limit)

J3

normally open

common

normally closed

L3

K3

Output 4 Mechanical Relay, Form A

common

normally open

A1

L4

Slot A

• 2 A at 240VÅ (ac) or 30VÎ (dc)

maximum resistive load

• 20 mV at 24V minimum load
• 125 VA pilot duty at 120/240VÅ

(ac), 25 VA at 24VÅ (ac)

• 100,000 cycles at rated load
• Output does not supply power.
• for use with ac or dc
See Quencharc note.
ST _ L - _ _ _ _ - _ _ _ _ (limit)

L4

A1

Advertising