Warning:

Use National Electric (NEC)

or other country-specific

standard wiring and safety

practices when wiring and

connecting this controller to

a power source and to elec-

trical sensors or peripheral

devices . Failure to do so may

result in damage to equip-

ment and property, and/or

injury or loss of life .

NOTE: To prevent ground

loops, isolation needs to be

maintained from input to out-

put when using switched DC

or analog process outputs .

CAUTION: Always mount the

controller with the heat-sink

fins aligned vertically .

NOTE: Terminals L4 and

A1 on the limit connector

are jumpered at the factory

to complete the contactor

circuit . Additional switches

may be wired in series to the

terminals .

Ó

WARNING: If high voltage is

applied to a low-voltage con-

troller, irreversible damage

will occur .

Watlow EZ-ZONE

®

ST

23

Chapter 2 Install and Wire

Quencharc Note:

Switching pilot duty inductive

loads (relay coils, solenoids,

etc .) with the mechanical

relay, solid state relay or

open collector output options

requires use of an R .C . sup-

pressor .

Digital Output 5 - 6

common

collector out

collector out

98
99

CF

CD
CE

B5
D6
D5

Slot C

• Internal supply pro-

vides a constant power

output of 750mW

• Maximum output sink

current per output is

1.5A (external class

2 or SELV supply re-

quired)

• Total sink current for

all outputs not to ex-

ceed 8A

• Do not connect outputs

in parallel

ST [B, C, D or E] _- _ _

_ _-_ _ _ _

B

24 Vdc

common

D

_

_

Quencharc Wiring Example

In this example the Quencharc
circuit (Watlow part# 0804-0147-
0000) is used to protect ST in-
ternal circuitry from the counter
electromagnetic force from the in-
ductive user load when de-enger-
gized. It is recommended that this
or an equivalent Quencharc be
used when connecting inductive
loads to ST outputs.

Quencharc

User Load

L_

K_

N