Analog input menu – Watlow EZ-ZONE ST User Manual

Page 33

Advertising
background image

Watlow EZ-ZONE

®

ST

31

Chapter 3 Operations Page

Operations Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative Ad-

dress

CIP

Class

Instance

Attribute

hex (dec)

Pro DP

Index

Par

ID

RUI/

GTW

Mod-

bus

Data

Type

& Read/

Write

[``Ai]
[oPEr]

Analog Input Menu

[``Ain]
[ Ain]

Analog Input (1 to 2)

Process Value

View the process value.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

Instance 1

Map 1 Map 2

- - - -

360

Instance 2

Map 1 Map 2
- - - -

450-

0x68 (104)

1 to 2

1

0

4001 Inst. 1

360

Inst. 2

520

float

R

No Dis-

play

Analog Input (1 to 2)

Filtered Process Value

View the filtered process

value.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

Instance 1

Map 1 Map 2

- - - -

402

Instance 2

Map 1 Map 2
- - - -

492-

0x68 (104)

1 to 2

0x16 (22)

0

4022 Inst. 1

402

Inst. 2

562

float

R

No Dis-

play

Analog Input (1)

Ambient Temperature

View ambient temperature.

-1,999.000 to 9,999.000°F

or units

-1,128.000 to 5,537.000°C

Instance 1

Map 1 Map 2

34

366

Instance 2

Map 1 Map 2
- - - -

492-

0x68 (104)

1

4

0

4004 Inst. 1

402

Inst. 2

562

float

R

[`i;Er]
[ i.Er]

Analog Input (1 to 2)

Error Status

View the cause of the most

recent error. If the [Attn]

message is [Er;i1] or
[Er;i2]

, this parameter will

display the cause of the in-

put error.

[nonE]

None (61)

[OPEn]

Open (65)

[Shrt]

Shorted (127)

[`E;M]

Measurement Er-

ror (149)

[E;CAL]

Bad Calibration

Data (139)

[Er;Ab]

Ambient Error (9)

[E;;Rtd]

RTD Error (141)

[FAiL]

Fail (32)

[NSrc]

Not Sourced (146)

None

Instance 1

Map 1 Map 2

41

362

Instance 2

Map 1 Map 2
69

452

0x68 (104)

1 to 2

2

1

4002 Inst. 1

362

Inst. 2

522

uint

R

No Dis-

play

Analog Input (1)

Clear Latched Input Er-

ror

Clear latched input.

Clear (0)
No Change (255)

Instance 1

Map 1 Map 2

68

416

Instance 2

Map 1 Map 2
96

506

0x68 (104)

1

0x1D (29)

0

4029 Inst. 1

416

uint

W

[`i;Ca]
[ i.CA]

Analog Input (1 to 2)

Calibration Offset

Offset the input reading to

compensate for lead wire re-

sistance or other factors that

cause the input reading to

vary from the actual process

value.

-1,999.000 to 9,999.000°F

or units

-1,110.555 to 5,555.000°C

0.0

Instance 1

Map 1 Map 2

51

382

Instance 2

Map 1 Map 2
79

472

0x68 (104)

1 to 2

0xC (12)

2

4012 Inst. 1

382

Inst. 2

542

float

RWES

Note:
Some values will be rounded off to fit in the four-character display . Full values can be

read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EE-

PROM

S: User

Set