Watlow EZ-ZONE ST User Manual

Page 30

Advertising
background image

Watlow EZ-ZONE

®

ST

28

Chapter 2 Install and Wire

that value to the control.
Communication Protocols
All EZ-ZONE ST controllers come standard with

the Standard Bus protocol. As a option it can also

be delivered with the Modbus protocol as well. The

Standard Bus protocol is used primarily for commu-

nications to other EZ-ZONE products to include the

RUI and EZ-ZONE Configurator software (free down-

load from Watlow's web site (

http://www.watlow.com

).

Other protocols that can be used to communicate

with the ST are available when used in conjunction

with the optional Remote User Interface/Gateway

(RUIGTW).
- Modbus RTU 232/485
- EtherNet/IP, Modbus TCP
- DeviceNet
- Profibus DP
If interested in learning more about the RUI/GTW

download the RUI/Gateway User Manual by pointing

your browser to:

http://www.watlow.com/literature/pti_search.cfm?dltype=5

Once there move to the bottom of the page and enter

EZ-ZONE into the Keyword field and then click the

search button.

Modbus RTU & Modbus TCP Protocols
All Modbus registers are 16-bits and as displayed in

this manual are relative addresses (actual). Some

legacy software packages limit available Modbus reg-

isters to 40001 to 49999 (5 digits). Many applications

today require access to all available Modbus registers

which range from 400001 to 465536 (6 digits). Watlow

controls support 6 digit Modbus registers. For param-

eters listed as float notice that only one (low order) of

the two registers is listed, this is true throughout this

document. By default the low order word contains the

two low bytes of the 32-bit parameter. As an example,

look in the Operations Page for the Process Value.

Find the column identified in the header as Modbus

and notice that it lists register 19 (instance 1, Map 1)

and register 360 (instance 1, Map 2). Because this pa-

rameter is a float instance 1 Map 1 is actually repre-

sented by registers 19 (low order bytes) and 20 (high

order bytes), likewise, instance 1 Map 2 is actually

represented by registers 360 (low order bytes) and

361 (high order bytes). Because the Modbus specifica-

tion does not dictate which register should be high

or low order Watlow provides the user the ability to

swap this order (Setup Page, [Com Menu) from the

default low/high [lohi] to high/low [hilo].

Note:

With the release of firmware revision 3.00 and

above new capabilities (phase angle control, user

programmable memory blocks, etc...) where intro-

duced into this product line. With the introduction

of these new capabilities there was a repacking of

Modbus registers. Notice in the column identified

as Modbus the reference to Map 1 and Map 2 reg-

isters for each of the various parameters. If the new

capabilities are to be used, be certain to select Map

2 Modbus registers. If the new functions of this

product line are not to be used, Map 1 (legacy ST

controls) Modbus registers will be sufficient. The

Modbus register mapping [map] can be changed

in the Setup Page under the [Com] Menu. This

setting will apply across the control.

It should also be noted that some of the cells in the

Modbus column as well as the RUI/GTW Modbus

column contain wording pertaining to an offset. Sev-

eral parameters in the control contain more than one

instance; such as, profiles (4), alarms (2), analog in-

puts (2), etc... The Modbus register shown always rep-

resents instance one. Take for an example the Step

Type [styp] parameter found in the Profile Page.

Instance one, Map 1, is shown as address 500 and

+20 is identified as the offset to the next instance. If

there was a desire to read or write to instance 3 sim-

ply add 40 to 500 to find its address. In this case, the

instance 3 address for Step Type is 540.
The ST control, when equipped with Modbus has user

programmable memory blocks. To learn more about

this feature click on the link or turn to the Features

section and look for the section entitled "

Modbus -

User Programmable Memory Blocks

".

Data Types Used with Modbus

unsigned

= Unsigned 16 bit integer

signed

= Signed 16-bit

float

= Float, IEEE 754 32-bit

long

= 32 bit unsigned integer

sint

= Signed 8 bits , byte

To learn more about the Modbus protocol point your

browser to

http://www.modbus.org

.

Common Industrial Protocol (CIP)

DeviceNet & Ethernet/IP
Both DeviceNet and EtherNet/IP use open object

based programming tools and use the same address-

ing scheme. In the following menu pages notice the

column header identified as CIP. There you will find

the Class, Instance and Attribute in hexadecimal,

(decimal in parenthesis) which makes up the ad-

dressing for both protocols.
The ST control has a feature that allows for implicit

messaging when used in conjunction with an RUI/

GTW equipped with a DeviceNet or EtherNet/IP

card. To learn more about this feature click on the

link or turn to the Features section and look for the

section entitled "

CIP - Communications Capabilities

".

Advertising