Current menu – Watlow EZ-ZONE ST User Manual

Page 38

Advertising
background image

Watlow EZ-ZONE

®

ST

36

Chapter 3 Operations Page

Operations Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative Ad-

dress

CIP

Class

Instance

Attribute

hex (dec)

Pro DP

Index

Par

ID

RUI/

GTW

Mod-

bus

Data

Type

& Read/

Write

No Dis-

play

Alarm (1 to 2)

Alarm Silenced

Indicates if alarm can be

silenced.

Yes (106)
No (59)

- - - -

Instance 1

Map 1 Map 2

1500 1900

Instance 2

Map 1 Map 2
1550

1960

0x6D

(109)

1 to 4

0x0B (11)

- - - -

9011

Inst. 1

1500

Inst. 2

1550

uint

R

No Dis-

play

Alarm (1 to 2)

Alarm Latched

Indicates if alarm is

latched.

Yes (106)
No (59)

- - - -

Instance 1

Map 1 Map 2

1498 1898

Instance 2

Map 1 Map 2
1548

1958

0x6D

(109)

1 to 4

0x0A (10)

- - - -

9010

Inst. 1

1498

Inst. 2

1548

uint

R

[CUrr]]
[oPEr]]

Current Menu

Note:
To use the current sensing feature, Time Base (Setup Page, Output
Menu) must be set to 0 .7 seconds or more .

[`C;hi]
[ C.hi]

Current (1)

High Set Point

Set the current value that

will trigger a high heater

error state.

-1,999.000 to 9,999.000

50.0

Instance 1

Map 1 Map 2

286

1254

0x73

(115)

1

8

- - - -

15008 Inst. 1

1134

float
RWES

[`C;Lo]
[ C.Lo]

Current (1)

Low Set Point

Set the current value that

will trigger a low heater er-

ror state.

-1,999.000 to 9,999.000

0.0

Instance 1

Map 1 Map 2

288

1256

0x73

(115)

1

9

- - - -

15009 Inst. 1

1136

float
RWES

[`CU;r]
[ CU.r]

Current (1)

Read

View the most recent cur-

rent value monitored by the

current transformer.

-1,999.000 to 9,999.000

Instance 1

Map 1 Map 2

38

1240

0x73

(115)

1

1

- - - -

15001 Inst. 1

- - - -

float
R

[`C;Er]
[ C.Er]

Current (1)

SSR Error

View the cause of the most

recent load fault.

[nonE]

None (61)

[Shrt]

Shorted (127)

[open]

Open (65)

None

Instance 1

Map 1 Map 2

40

1242

0x73

(115)

1

2

- - - -

15002 Inst. 1

1122

uint
R

[`h;Er]
[ h.Er]

Current (1)

Heater Error

View the cause of the most

recent load fault monitored

by the current transformer.

[nonE]

None (61)

[high]

High (37)

[Low]

Low (53)

None

Instance 1

Map 1 Map 2

282

1244

0x73

(115)

1

3

- - - -

15003 Inst. 1

1124

uint
R

No Dis-

play

Current (1)

Error Status

View the cause of the most

recent load fault

[none]

None (61)

[fail]

Fail (32)

- - - -

Instance 1

Map 1 Map 2

1160 1400

0x73

(115)

1

21

- - - -

15021

- - - - uint

R

Note:
Some values will be rounded off to fit in the four-character display . Full values can be

read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EE-

PROM

S: User

Set