Chapter 3 Operations Page

Operations Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative Ad-

dress

CIP

Class

Instance

Attribute

hex (dec)

Pro DP

Index

Par

ID

RUI/

GTW

Mod-

bus

Data

Type

& Read/

Write

[P;Sta]
[oPEr]

Profile Status Menu

* Some parameters in the Profile Status Menu can be changed for the currently running profile,

but should only be changed by knowledgeable personnel and with caution. Changing param-

eters via the Profile Status Menu will not change the stored profile but will have an immediate

impact on the profile that is running.

Changes made to profile parameters in the Profiling Pages will be saved and will also have an

immediate impact on the running profile.

[P;Str]
[P.Str]

Profile Status

Profile Start

1 to 40

1

Instance 1

Map 1 Map 2

292

3800

0x7A

(122)

1
1

204

22001 Inst. 1

2898

Offset

+ 80

uint
RWE

[P;ACr]
[PACr]

Profile Status

Action Request

[nonE]

None (61)

[ProF]

Profile (77)

[PAUS]

Pause (146)

[rESU]

Resume (147)

[`End]

Terminate (148)

[step]

Step (89)

None

Instance 1

Map 1 Map 2

306

3820

0x7A

(122)

1

0xB (11)

205

22011 Inst. 1

2920

Offset

+ 80

uint
RW

[`StP]
[ StP]

Profile Status

Active Step

View the currently running

step.

1 to 40

0 (none)

Instance 1

Map 1 Map 2

296

3806

0x7A

(122)

1
4

- - - -

22004 Inst. 1

2906

Offset

+ 80

uint
R

[S;typ]
[S.typ]

Profile Status

Active Step Type

View the currently running

step type.

[UStP]

Unused Step

(50)

[``ti]

Time (143)

[rAtE]

Rate (81)

[SoAH]

Soak (87)

[w;e]

Wait for Event

(144)

[w;pr]

Wait for Pro-

cess(209)

[CloC]

Wait for Time

(1543)

[``JL]

Jump Loop (116)

[`End]

End (27)

- - - -

Instance 1

Map 1 Map 2

- - - - 3824

0x7A

(122)

1

0xD (13)

- - - -

22013 Inst. 1

2924

Offset

+ 80

uint
R

[t;SP1]
[tg.SP]

Profile Status

*Target Set Point Loop 1

View or change the target

set point of the current

step.

-1,999.000 to

9,999.000°F or units

-1,128.000 to

5,537.000°C

0.0°F

or

units

-18.0°C

Instance 1

Map 1 Map 2

- - - - 3822

0x7A

(122)

1

0xC (12)

- - - -

22012

- - - - uint

RW

[P;SP1]
[P.SP1]

Profile Status

Produced Set Point 1

Display the current set

point, even if the profile is

ramping.

-1,999.000 to

9,999.000°F or units

-1,128.000 to

5,537.000°C

0.0°F

or

units

-18.0°C

Instance 1

Map 1 Map 2

297

3808

- - - -

- - - -

22005 Inst. 1

2908

Offset

+ 80

float
R

[hour]
[hour]

Profile Status

Hours Remaining

0 to 99

0.0

Instance 1

Map 1 Map 2

- - - - - - - -

- - - -

- - - -

22078

- - - - - - - -

[min]
[Min]

Profile Status

Minutes Remaining

0 to 59

0.0

Instance 1

Map 1 Map 2

- - - - - - - -

- - - -

- - - -

22077

- - - - - - - -

Note:
Some values will be rounded off to fit in the four-character display . Full values can be

read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EE-

PROM

S: User

Set