Chapter 5 Profile Page

Profile Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Pro DP

Index Par ID

RUI/

GTW

Mod-

bus

Data

Type

&

Read/

Write

[S;typ]
[S.typ]

Step (1 to 40)

Step Type

Select a step type.

Time or rate depending

on setting of profile type

found on the Setup Page in

the the Global menu.

[UStP]

Unused Step (50)

[``ti]

Time (143)

[`End]

End

[``JL]

Jump Loop (116)

[w;bo]

Wait For Both (210)

[w;pr]

Wait For Process

(209)

[`w;E]

Wait For Event

(144)

[SoAH]

Soak (87)

[rAtE]

Rate (81)

Unused

Instance 1

Map 1 Map 2

500

4000

[Map1 Offset

+ 20]

[Map2 Offset

+ 100]

0x79

(121)

1 to (40)

1

- - - -

21001 Inst. 1

2870

Offset

+80

uint

RWE

[t;SP1]
[t.SP1]

Step (1 to 40)

Target Set Point Loop 1

Set the set point for this

loop.

-1,999.000 to 9,999.000 ºF

or -1,128.000 to 5,537.000

ºC

0.0

Instance 1

Map 1 Map 2

501

4002

[Map1 Offset

+ 20]

[Map2 Offset

+ 100]

0x79

(121)

1 to (40)

2

- - - -

21002 Inst. 1

2872

Offset

+80

float

RWE

[hoUr]
[hoUr]

Step (1 to 40)

Hours

Select the hours (plus

Minutes and Seconds) for a

timed step.

0 to 99

0

Instance 1

Map 1 Map 2

503

4004

[Map1 Offset

+ 20]

[Map2 Offset

+ 100]

0x79

(121)

1 to (40)

3

- - - -

21003 Inst. 1

2874

Offset

+80

uint

RWE

[Min]
[Min]

Step (1 to 40)

Step Type Parameters

Minutes

Select the minutes (plus

Hours and Seconds) for a

timed step.

0 to 59

0

Instance 1

Map 1 Map 2

504

4006

[Map1 Offset

+ 20]

[Map2 Offset

+ 100]

0x79

(121)

1 to (40)

4

- - - -

21004 Inst. 1

2876

Offset

+80

uint

RWE

[~SEC]
[ SEC]

Step (1 to 40)

Seconds

Select the seconds (plus

Hours and Minutes) for a

timed step.

0 to 59

0

Instance 1

Map 1 Map 2

505

4008

[Map1 Offset

+ 20]

[Map2 Offset

+ 100]

0x79

(121)

1 to (40)

5

- - - -

21005 Inst. 1

2878

Offset

+80

uint

RWE

[rate]
[rAtE]

Step (1 to 40)

Rate

Select the rate for ramp-

ing in degrees or units per

minute.

0 to 9,999.000°F or units

per minute

0 to 5,555.000°C per min-

ute

0.0

Instance 1

Map 1 Map 2

506

4010

[Map1 Offset

+ 20]

[Map2 Offset

+ 100]

0x79

(121)

1 to (40)

6

- - - -

21006 Inst. 1

2880

Offset

+80

float

RWE

Note:

Some values will be rounded off to fit in the four-character display . Full values can be
read

with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EE-

PROM

S: User

Set