Alarm menu – Watlow EZ-ZONE ST User Manual

Page 37

Advertising
background image

Watlow EZ-ZONE

®

ST

35

Chapter 3 Operations Page

Operations Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative Ad-

dress

CIP

Class

Instance

Attribute

hex (dec)

Pro DP

Index

Par

ID

RUI/

GTW

Mod-

bus

Data

Type

& Read/

Write

[ALM]
[oPEr]

Alarm Menu

[`A;Lo]
[ A.Lo]

Alarm (1 to 2)

Low Set Point

If Alarm Type (Setup Page,

Alarm Menu) is set to:

process - set the process

value that will trigger a

low alarm.

deviation - set the span of

units from the closed loop

set point that will trigger

a low alarm.

-1,999.000 to

9,999.000°F or units

-1,128.000 to

5,537.000°C

32.0°F

or

units

0.0°C

Instance 1

Map 1 Map 2

99

1452

Instance 2

Map 1 Map 2
115

1512

0x6D

(109)

1 to 2

2

18

9002 Inst. 1

1482

Inst. 2

1532

float
RWES

[`A;hi]
[ A.hi]

Alarm (1 to 2

High Set Point

If Alarm Type (Setup Page,

Alarm Menu) is set to:

process - set the process

value that will trigger a

high alarm.

deviation - set the span of

units from the closed loop

set point that will trigger

a high alarm.

-1,999.000 to

9,999.000°F or units

-1,128.000 to

5,537.000°C

300.0°F

or

units

150.0°C

Instance 1

Map 1 Map 2

97

1450

Instance 2

Map 1 Map 2
113

1510

0x6D

(109)

1 to 2

1

19

9001 Inst. 1

1480

Inst. 2

1530

float
RWES

No Dis-

play

Alarm (1 to 2)

Alarm State

Read current state of alarm

Startup (88)
None (61)
Blocked (12)
Alarm low (8)
Alarm high (7)
Error (28)

None

Instance 1

Map 1 Map 2

29

1466

Instance 2

Map 1 Map 2
30

1526

0x6D

(109)

1 to 2

9

- - - -

9009 Inst. 1

1496

Inst. 2

1546

uint

R

No Dis-

play

Alarm (1 to 2)

Alarm Clearable

Indicates if alarm can be

cleared.

[``no]

No (59)

[`YES]

Yes (106)

None

Instance 1

Map 1 Map 2

- - - - 1472

Instance 2

Map 1 Map 2
- - - -

1532

0x6D

(109)

1 to 2

0xC (12)

- - - -

9012 Inst. 1

1502

Inst. 2

1552

uint

R

No Dis-

play

Alarm (1 to 2)

Alarm Clear Request

Write to this register to

clear an alarm

Clear (0)
No Change (255)

None

Instance 1

Map 1 Map 2

108

1474

Instance 2

Map 1 Map 2
124

1534

0x6D

(109)

1 to 2

0xD (13)

32

9013 Inst. 1

1504

Inst. 2

1554

uint

W

No Dis-

play

Alarm (1 to 2)

Alarm Silence Request

Write to this register to

silence an alarm

Clear (0)
No Change (255)

None

Instance 1

Map 1 Map 2

109

1476

Instance 2

Map 1 Map 2
125

1536

0x6D

(109)

1 to 2

0xE (14)

33

9014 Inst. 1

1506

Inst. 2

1556

uint

W

Note:
Some values will be rounded off to fit in the four-character display . Full values can be

read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EE-

PROM

S: User

Set