User’s guide, Battery management system – APC Battery Management System User Manual

Page 174

Advertising
background image

®

USER’S GUIDE

Battery Management System

167

3. Run a terminal program (such as HyperTerminal), and configure the

selected port for 9600 bps (or 19200 bps), 8 data bits, no parity, 1 stop
bit, and no flow control, and save the changes.

4. Press

E

NTER

to display the

User Name

prompt.

5. Enter your Administrator user name and password. The default for

both is

apc

.

6. Start an XMODEM transfer:

a. Select option 3—

System

b. Select option 4—

File Transfer

c. Select option 2—

XMODEM

d. Type Yes at the prompt to continue with the transfer.

7. Select the appropriate baud rate. A higher baud rate causes faster

firmware upgrades. Also, change the terminal program’s baud rate to
match the one you selected, and press

E

NTER

.

8. From the terminal program’s menu, select the binary AOS file to

transfer via XMODEM-CRC. After the XMODEM transfer is complete,
set the baud rate to 9600. The Management Card will automatically
restart.

9. Repeat

step 3

through

step 8

to install the application module. In

step

8

, substitute the application module file name for the AOS module file

name.

For information about the format used for application modules,
see

Firmware files (Battery Management System)

.