User’s guide, Battery management system – APC Battery Management System User Manual

Page 32

Advertising
background image

®

USER’S GUIDE

Battery Management System

25

Management Controller alarms.

Charge Test

When the Battery
Management System applied
a test current, the batteries
listed in the alarm message
showed a higher than
acceptable percentage
deviation from the previous
“benchmarked” values (which
are reset after any
discharge).

Problem:

A percentage deviation

outside the acceptable range indicates
unexplained changes that indicate the
need to verify possible problems with the
battery.

Response:

Identify the listed batteries

immediately so that system backup time
is not reduced. Test and verify status of
the identified batteries immediately.

Pilot
Temperature
s

Sampling of the surface
temperature of one battery in
the string showed a
temperature above the
configured threshold.

Default:

95° F (35° C) (high
threshold).

Problem:

A high temperature alarm may

indicate an overheated (overcharged)
battery, usually caused by a faulty
charger.

Response:

If uncorrected, this condition

can cause permanent damage to the
batteries. Replace failed batteries.

Category

Details

Diagnostics

Blown
Connection
Fuse

The connections between the
Management Controller and
the batteries are open.

Problem:

One or more fuses or wires

are open.

Response:

Replace the fuse or wire

connection in the location indicated in
the event log.

Missing or
Defective
Sensors

Not all sensors are present
and functional.

Problem:

The system operation is

not reliable without sensor
information.

Response:

Connect or replace the

sensor indicated in the event log.

Category

Details

Diagnostics