Snmp issues (battery management system management, Card), User’s guide – APC Battery Management System User Manual

Page 180: Battery management system

Advertising
background image

®

USER’S GUIDE

Battery Management System

173

SNMP issues (Battery Management System
Management Card)

Problem

Solution

Unable to perform a GET

1. Verify the read (GET) community name.
2. Use the Control Console or Web interface to ensure

that the NMS has access. See

Telnet/SSH

.

Unable to perform a SET

1. Verify the read/write (SET) community name.
2. Use the control console or Web interface to ensure

that the NMS has write (SET) access. See

Telnet/

SSH

.

Unable to receive traps at
the NMS

Query the MIB

mconfigTrapReceiverTable

OIDs to

verify that the NMS IP address is listed correctly, and
that the community name defined for the NMS matches
the community name in the table. If necessary, use SETs
to the OIDs, or use the control console or Web interface
to correct the trap receiver definition problem. See

Telnet/SSH

.

Traps received at an NMS
are not identified

See your NMS documentation to verify that the traps are
properly integrated in the alarm/trap database.