Calibration menu, User’s guide, Battery management system – APC Battery Management System User Manual

Page 36

Advertising
background image

®

USER’S GUIDE

Battery Management System

29

Calibration menu

Select to calibrate either a

String

or a

Unit.

String.

Select the string you wish to calibrate.

Unit.

Select the unit you wish to calibrate.

String X

Each string will be listed. Select the
string you wish to configure

Ohmic Correction

Set the overall Ohmic Correction
value.

Unit X (Web interface)

Each unit will be listed.

DC Voltage Zero

Set to zero with no string current.

DC Voltage Span

Set to 100, 200, 500, or 1000 A full
scale.

AC Ripple Zero

Set to zero with no string current.

Ohmic Correction

Set to match calibrated instrument.

Current Sensor Range

Set to 100, 200, 500, or 1000 A full
scale, based on current sensor
specifications.

DC Current Sensor Zero

Set to zero with no string current.

AC Current Sensor Zero

Set to zero with no string current.

Tier Ohmic Value

Enter milliohms of cables and
connectors within the string to match
calibrated instrument.