Management Card and Battery Manager Events

Event generation

The Management Card and Battery Management System both generate
events, which are logged in the event log.

Any event of either type generates a unique code, which you can use in
applications to identify the event.

To use

SNMP

traps for event notifications, you must first identify the trap

receivers (up to four) by their specific IP addresses.

Discharge cycle counter

Battery management event 0x0814 alerts you that a battery string is
discharging, and displays the string current (rate of discharge), ambient and
pilot battery temperatures. Battery management event 0x0815 indicates
that the battery string is no longer discharging.

The system automatically records the ampere-hours lost by the battery
string during the discharge.