Alarm relay and led operation, User’s guide, Battery management system – APC Battery Management System User Manual

Page 177

Advertising
background image

®

USER’S GUIDE

Battery Management System

170

Alarm Relay and LED Operation

Situation/Condition

Alarm Relay

Status LEDs

N

OTE

:

Alarm Relay

operates as a “Fail-
Safe” device that is
energized during
non-alarmed periods.

Normally Open
Contacts (de-
energized)

Management
Controller

Batteries

Charger

Environment

Normal Operations

Closed
(energized)

On

On

On

On

Management System
Fault

Open
(de-energized)

Flash

On

On

On

High or low
environment
temperature or
auxiliary environment
sensor alarm

Open
(de-energized)

On

On

On

Flash

Charger Fault - High
or low charging
voltage or high ripple
current

Open

On

On

Flash

On

Connection fuse or
wiring fault

Open

Flash

On

On

On

Battery Fault - Low
capacity, high ohmic
value, shorted cell or
thermal runaway

Open

On

Flash

On

On

Missing or Faulty
Sensor

Open

Flash

On

On

On

System off or loss of
input power

Open

Off

Off

Off

Off