The following specific information may be shown on the display during calibration:
Information displayed
Description
SHORTCIRCUIT TEST LEADS
AND PRESS START KEY TO
CALIBRATE
Calibration has been started (CAL touch-screen key has
been pressed).
Shortcircuit test leads and press the START button!
OPEN TEST LEADS,
CALIBRATION ANNULED
Test leads are opened after pressing the START button.
Press YES key … existing calibration will be annulled!
Press NO key … existing calibration will stay untouched!
RPE > 5
CALIBRATION FAILED
Connected resistance is higher than 5
and lower than
measurement range, calibration can not be carried out.
Existing calibration will stay untouched.
Reduce external resistance and repeat the calibration!
5.1.3. LIMIT VALUE ADJUSTMENT
Test current 200 mA is selected:
Limit value can be selected within the range from 0.01 up to 99.99
in steps of 0.01 .
Test current 25 A is selected:
There are three possibilities to select the limit value.
- STANDARD selection.
Limit value can be selected within the range from 0.
01 up to 20.00
in steps of 0.01 .
- EN60204 SET L selection.
Limit value is calculated on bases of wire length (L), wire section (SECTION) and wire material
(MATERIAL), where the parameters can be selected/adjusted within the following ranges:
- L (length)
0.1 up to 999.9 m in steps of 0.1 m
- SECTION (wire section)
1, 2.5, 4, 6, 10, 16, 25, 35, 50 or 70 mm
2
- MATERIAL (wire material) Cu (Copper) or Al (Aluminium)
- EN60204 SET Z selection.
Limit value is calculated on bases of entered line
impedance (Z
LINE
), type
of protection (TYPE),
nominal current (I
N
) and wire section (SECTION), where the parameters can be selected within the
following ranges:
- Zline (line impedance)
0.001
up to 2.000
in
steps of 0.001
- TYPE (type of protection) MCB B, MCB C, MCB D, MCB K, FUSE gG or FUSE aM
- In (nominal current)
- 6, 10, 13, 16, 20, 25, 32, 40, 50 or 63 A (MCB B)
- 0.5, 1, 1.6, 2, 4, 6, 10, 13, 16, 20, 25, 32, 40, 50 or 63 A (MCB C)
- 0.5, 1, 1.6, 2, 4, 6, 10, 13, 16, 20, 25 or 32 A (MCB D, MCB K)
-
2, 4, 6, 8, 10, 12, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160,
200, 250, 315, 400, 500, 630, 800, 1000 or 1250 A (FUSE gG)
-
2, 4, 6, 8, 10, 12, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 160,
200, 250, 315, 400, 500 or 630 A (FUSE aM)
- SECTION (wire section)
1, 2.5, 4, 6, 10, 16, 25, 35, 50 or 70 mm
2